Antenna Relocation Diagram
5.4
UL Requirements
5.4.1 Grade A - Central Station Service, Residential Fire 
and Burglary Installations
• Programming [13] - Option 2 Test Rates must be “ON”.
• Every 24 hours a check-in signal must be sent to the central
station. Refer to compatible Listed control unit’s installation
instructions for programming.
• Dialing attempts must be programmed for 5 to 10 attempts.
Skyroute transmitter makes 3 attempts by default. Refer to
compatible Listed control unit’s installation instructions for
programming.
• The response wait time, section [24] should be set to 09.
• Alarm signals must be sent over both primary and secondary
communication paths -
1. Compatible Listed control unit’s land line to central sta-
tion (primary).
2. Skyroute transmission through Cellemetry to the clearing
house (Connect 24) (secondary).
• DACT must be enabled for Listed compatible control unit.
5.4.2 Police Station Connect with Basic Line Security
• Same as Grade A Central Station Installations.
5.4.3 Commercial Fire Installations
• Same as Grade A Central Station Installations.
• The BELL+ and BELL- terminals on the control panel shall
not power other devices. Refer to Compatible Listed control
unit installation instructions for wiring and programming.
5.4.4 Back-up Reporting Mode (03) 
• To be used only for UL/ULC residential Fire and Burglary
applications.
5.4.5 For ULC Installations
• The redundant Communication mode (00) meets level 2 line
security requirements.
Antenna Extension Kits
LAE-3
3-ft. (0.9m) extension kit
LAE-15
LAE-25
SKR-025
15-ft. (4.6m) extension kit
25-ft. (7.6m) extension kit
25-ft. (7.6m) extension kit (external)