TransCore 0596465PT15 Manuel D’Utilisation
Installing the Encompass 4H Reader
4-27
Sense Output Circuits
The Encompass 4H Reader supports three sets of sense output signals. Two sets
–
sense output0 and sense output1
–
provide NO or NC sense outputs. The third sense
output set is dedicated for testing and set up of the reader. It is defined as the
TAG_LOCK signal, which indicates a valid tag is in the read field.
TAG_LOCK signal, which indicates a valid tag is in the read field.
These sense outputs are dry contacts that provide NO and NC sense outputs. The relay
contacts are rated at 42.2V AC peak (30 V
contacts are rated at 42.2V AC peak (30 V
rms
) or 60V DC at 1 A maximum. If con-
trolling an external gate or device requiring high current, an isolation transformer is
required.
required.
As illustrated in
, sense output0, NC, is located on the orange/black pair.
Sense output0, NO, is located on the brown/black pair.
As shown in
, for IAG applications, Sense output0 NC, shares a common
return with sense output0 NO.
In Wiegand mode operation, the sense outputs are not controlled by a predefined out-
put mode.
put mode.
lists the cable descriptions and functions for the interface signals. These
wire pairs can be used or terminated based on the specific project applications and site
requirements.
requirements.