Installing the Encompass 4H Reader
4-27
Sense Output Circuits 
The Encompass 4H Reader supports three sets of sense output signals. Two sets 
 
sense output0 and sense output1 
 provide NO or NC sense outputs. The third sense 
output set is dedicated for testing and set up of the reader. It is defined as the 
TAG_LOCK signal, which indicates a valid tag is in the read field.
These sense outputs are dry contacts that provide NO and NC sense outputs. The relay 
contacts are rated at 42.2V AC peak (30 V
rms
) or 60V DC at 1 A maximum. If con-
trolling an external gate or device requiring high current, an isolation transformer is 
required.
As illustrated in 
, sense output0, NC, is located on the orange/black pair. 
Sense output0, NO, is located on the brown/black pair.
As shown in 
for IAG applications, Sense output0 NC, shares a common 
return with sense output0 NO.
In Wiegand mode operation, the sense outputs are not controlled by a predefined out-
put mode.
 lists the cable descriptions and functions for the interface signals. These 
wire pairs can be used or terminated based on the specific project applications and site 
requirements.