Rosslare Enterprises Ltd 20A302 Manuel D’Utilisation

Page de 2
Rosslare
Installation Instructions
Model Series AY-Q12
03/02
MOUNTING INSTRUCTION
To mount the Reader, perform the following:
Determine an appropriate mounting position for the Reader.
Peel off the back of the self-stick mounting label template
included with the unit and place at the desired mounting position.
Using the template as a guide, drill two holes (hole size is
indicated on mounting template) for mounting the Reader to the
surface. Drill a 7/16" (10mm) hole for the cable. If mounting on
metal, place a grommet around the edge of the hole.
Remove the case screw and slide the rear case away from the front
case. (See diagram below)
Drill holes into the back of the rear metal case according to how
you want to mount the reader. (See Diagram below)
Attach the reader to the controller.
Screw the readers rear case to its mounting location and return the
front case onto the mounted rear case.
Secure the front cover by using the supplied security screw in the
controllers accessories kit. An L-Shaped tool is provided for use
when tightening the security screw.
1.
2.
3.
4.
5.
6.
7.
8.
After the card data is processed by the Controller, the Controller
can then turn the LED green. Refer to the Controller description
of the LED operation if the Reader LED is controlled by the
Controller.
3.
-1-
Measured using Rosslare Proximity Card (P/N AT-11/14) or
equivalent. Range also depends on electrical environment and/or
proximity to metal.
*
Figure 2
WIRING INSTRUCTION
The Prox Reader is supplied with an 18-inch pigtail, having a 6-
conductor cable. To connect the Reader to the Controller, perform
the following steps:
Prepare the Reader cable by cutting the cable jacket back 1
inches and strip the wires
inch.
Prepare the Controller cable by cutting the cable jacket back 1
inches and strip the wires
inch.
Splice the Reader pigtail wires to the corresponding Controller
wires and cover each connection (see Figure 2).
If the tamper output is being utilized, connect the purple wire to
the correct input on the Controller.
Trim and cover all conductors that are not used.
1/4
1/2
1/4
1/2
1.
2.
3.
4.
5.
Figure 2 below shows how you should wire the Reader to the
Controller.
Cable Notes:
The individual wires coming out of the reader are color coded according
to the recommended Wiegand standard.
When using a separate power supply for the Reader, this supply and the
Controller's power supply must have a common ground.
The cable shield wire on the Reader should be attached to an Earth
ground (best) or signal ground connection at the panel or power supply
end of the cable. This configuration is best for shielding the Reader
cable from external interference.
1.
2.
3.
OPERATION INSTRUCTION
The Reader should be tested after wiring it to a power supply and the
Controller. Do this by performing the following steps:
Power up the Reader. The LED and Beeper will activate three
times. This indicates that the Reader is working properly.
Present the appropriate type of proximity card to the Reader. The
LED will momentarily flash green and a short beep will be
emitted. This indicates that the card was read properly by the Prox
Reader..
1.
2.
COLOR
Red
Black
White
Green
Brown
Purple
WIEGAND
OUTPUT
DC+Input
Ground
Data 1
Data 0
LED Control
Tamper
-2-
Card Readers are to be used with control panels whose power
supply is UL Listed Class 2 or equivalent.
-3-
SPECIFICATIONS
Power Supply Type
Operating Voltage Range
Linear type recommended
5 - 16 VDC
Maximum Input Current
Tamper Output
Maximum Cable Distance
to Controller
RF Modulation
Open collector, active low,
max. sink current is 16 mA
150 meters (500 ft.)
ASK
Card Read Distance:
Regulatory Approvals:
Operating Temp. Range:
Operating Humidity:
Dimensions:
USA : UL 294 & FCC Part 15B
Europe : CE Listed
-31 C to 63 C (-25 F to 145 F)
o
o
o
o
0 to 95% (non condensing)
Standby : 35 mA
Read : 100 mA
UL File Number: BP9264
Suitable for outdoor use
The AY-Q12 Prox Reader is a weather and
vandal resistant RFID proximity card
reader, to be installed for use with access
control systems.
These Installation Instructions contain the
following information:
* Mounting Instructions
* Wiring Instructions
* Operation Instructions
A
A
B
B
B
B
CAUTION!
DO NOT DRILL
This is the Tamper Lens
US Gang Box
4 Screw Custom
There are two hole
indicators on the back of
the metal cover
specifically for the US
Gang Box. (Shown
marked as A)
There are four indicators
on the back. (Shown
marked as B)
Output Modulation
26-Bit Wiegand
*
4.72” (120mm) L x 3” (76mm) W x 1” (27mm) D
-1-
2” (55mm)
0706-0820022-00