Installation Manual
Installation Manual
Senzafil Control Unit
1. Mounting Instructions
The control unit has a construction with the ability to mount on a DIN rail.
Nedap recommends to use the Nedap Light Controls
Box to build-in the control unit.
(Nedap p/n …………..)
2. Connections
Details inputs and outputs
+24V*
+
+24Vdc / 2% power input
Input
current:
0.3Adc
max
- gnd
RS232
RS232
Optional
CAN
Optional
Group 1..8
ON
ON/OFF Input
Closed=ON
Open=OFF
Levels: <3.5Vdc OFF and >4.5Vdc ON
DIM
DIM Input (Source current: 1mA (for light sensors))
Via
switch:
Closed=50%
Open=100%
Via 10kΩ potmeter:
0kΩ=50% 10kΩ=100%
Via
1-10V
Light
Sensor:
1V=50%
10V=100%
Via
1-10V
PLC/BMS:
1V=50%
10V=100%
ERR
Error
Output
Contact
to
gnd:
30V/2A
max
* NOTE: Use isolated 24Vdc limited power supply with 2.5A max current. For US/Canada use a listed class 2 power
supply. (e.g. MAIN WELL type GS15E-6P1J)
+24Vdc
ON inputs
+24Vdc
Indicator
To e.g. PLC
OR
Use of error contact
1-10V DIM inputs
Note: The control unit must never be
installed in a metal power cabinet. This
would impede wireless communication.