Product Data RBS 2206
Table 54
AC mains power requirements
Voltage range for specified
performance (phase voltage)
120 - 250 V AC
Voltage range
108
(1)
-275 V AC
Frequency
45 - 65 Hz
Inrush current, max.
30 A
Maximum AC power
1.4 kW x 4
Non-destructive range
0 – 300 V AC
Overvoltage <20 ms
300 V
(2)
(1) 90 V AC with reduced output power.
(2) Install external filter and stabilizer if not met.
Mains Fuses
Table 55
Mains fuses recommendation
Voltage
Minimum for Safe
Function
Maximum Allowed
Fuse Rating
Nominal 120 - 250 V
10 A
(1)
/15 A
16 A
(1) For 200 - 250 V range only
Minimum for safe value means the smallest fuse that can be used with
respect to power consumption and start up current.
Maximum allowed must not be exceeded due to the dimensions of the
internal wiring and components.
AC Power Cables
There are four external power cables for the radio cabinet, one for each
Power Supply Unit. They are connected to the ACCU main switch with
screw terminals.
The conductor area can be 1.5 – 2.5 mm
2
and the cable diameter can be
8.5 – 12.5 mm.
6.3.2
+24 V DC Power Supply
DC Power Supply Requirements (+24 V)
Table 56
DC power supply requirements
Nominal
+24 V DC
Default
+27.2 V DC
Range
+20.5 – +29.0 V DC
Non-destructive range
+0 - +32.0 V DC
Inrush current
max. 500 A (0.1 - 10 ms)