Cinch Systems Inc RF-ROR-433 Manuel D’Utilisation

Page de 2
 
HDX-135-433 
 
HDX-135-433
 
    Wireless Rate-of-Rise Heat Detector Installation Instructions 
 
Introduction 
The HDX-135-433 wireless heat detector uses electronic 
processing to detect both heat and freeze conditions plus a 
wireless transmitter (433MHz) in one unit. The micro-
processor trips the transmitter when the temperature at the 
detector location reaches a fixed temperature of 135°F 
(57°C), or senses a rate of rise at 12°F to 15ºF (6.7 to 8.3ºC) 
 
Figure 1 
 
Models 
HDX-135-433 
Wireless 135°F (57°C) Rate-of-Rise    
Heat Detector 
 
Installation 
Use the following installation guidelines:  
• 
Heat detectors should be installed to provide property 
protection. Reliance should not be placed on heat 
sensors for life safety. Where life safety is involved, 
smoke sensors must also be installed.   
• 
Mount the detector in a central location of the area to be 
protected, either on the ceiling or on a wall.  
• 
If mounting on a ceiling, the detector must be at least 4 
in. (10 cm) away from any walls.  
• 
If mounting on a wall, the top of the detector must be 
within 4 to 6 in. (10 to 15 cm) of the ceiling. 
• 
The UL maximum spacing allowance of the detector is 
50 x 50 ft. (15 x 15 m). Refer to the NFPA Standard 72 
for application requirements. 
• 
Do not mount the detector close to devices that change 
temperature rapidly, such as ovens, heat vents, 
furnaces, or boilers. 
 
Programming 
The panel must program the detector ID code in order to respond to 
detector signals. 
 
Note: For complete programming information, refer to the specific 
control panel documentation.  
 
To add the sensor to panel memory: 
 
1.  Place the panel in program mode.  
2.  Proceed to the section in programming for enrolling 
wireless sensors.  
3.  When the panel prompts enter the senor ID# or trip the 
sensors tamper  
 
Figure 2: Tamper 
 
4.  Exit Program Mode 
 
Mounting the Detector 
1.  Locate the base mounting holes and mount the base to 
the wall or ceiling with the appropriate hardware (Figure 
3) 
2.  Attach the detector to the mounting base 
 
 
Figure 3: Mounting Holes 
 
 
Testing 
1.  Before permanently securing the detector to the wall or 
ceiling, test the detector from the installation location 
using one of the following methods.  
2.  Place the panel in sensor test mode.  
3.  Plug in a portable hair dryer.  
4.  Hold the hair dryer about 12 to 18 in. away from the 
sensor, aiming it at the side of the sensor.  
5.  Listen for the appropriate number of beeps from interior 
sirens and speakers (refer to the specific panel 
documentation).  
6.  To test the freeze sensor, use either freeze spray or 
place an ice cube in a plastic bag and hold against the 
sensor until the device trips. 
7.  Listen for the appropriate number of beeps from interior 
sirens and speakers 
 
 
Tamper 
Mounting 
Holes