GOAP d.o.o. Nova Gorica BZW100A0 Manuel D’Utilisation

Page de 3
 
                   
 
 
Qubino
 
 
       
 
The INNOVATIVE and SMALLEST
                 
 
 
Flush Dimmer 0-10V  
 
ORDERING CODE 
Z-WAVE FREQUENCY 
ZMNHVD1   
868,4 MHz 
ZMNHVD2  
921,4 MHz 
ZMNHVD3  
908,4 MHz 
ZMNHVD4   
869,0 MHz 
ZMNHVD5  
916,0 MHz 
ZMNHVD8  
865,2 MHz 
 
Universal dimmer module with a standard 0-10V output 
and a multi-function input, which may be a push button / 
switch, a potentiometer or 0-10V signal 
 
Supported control types 
 
Push button (mono stable switch) 
 
Bi stable switch  
 
Potentiometer 
 
0-10V input (requires external source) 
 
Installation
 
 
Before  the  installation  disconnect  power  supply  (12-
24VDC) 
 
Connect the module according to electrical diagram.  
 
Locate  the  antenna  far  from  metal  elements  (as  far 
as possible).  
 
Do not shorten the antenna. 
 
Danger of electrocution!  
 
Module  installation  requires  a  great  degree  of  skill 
and  may  be  performed  only  by  a  qualified  and 
licensed electrician. 
 
Even when the  module is turned off, voltage may be 
present  on  its  terminals. Any  works  on  configuration 
changes related to connection mode or load must be 
always  performed  by  disconnected  power  supply 
(disable the fuse). 
 
Note! 
Do  not  connect  the  module  to  loads  exceeding 
recommended  values.  Connect  the  module  only  in 
accordance  to  the  below  diagrams.  Improper  connections 
may be dangerous. 
 
 
For overload protection use fuse F (ESKA 522.504 
50mA 250V) according to Electrical diagram.
 
 
Package contents: 
 
Flush Dimmer 0-10V 
 
 
Electrical diagram  
 
 
 
 
 
 
 
 
 
 
 
 
 
Notes for the diagram:
 
+ 
12 - 24VDC 
 
GND 
AO 
0 - 10VDC 
I1 
Input for push button/switch/potentiometer or 0-
10V 
TS 
Terminal for digital temperature sensor (only for 
Flush Dimmer 0-10V  module compatible digital 
temperature  sensor,  which  must  be  ordered 
separately). 
 
 
 
 
 
 
Module 
Inclusion  (Adding  to  Z-Wave 
network) 
 
Connect module to power supply (with  
temperature sensor connected - if purchased), 
 
enable add/remove mode on main controller 
 
auto-inclusion  (works  for  about  5  seconds  after 
connected to power supply) or 
 
press service button S for more than 2 second or 
 
press  push  button  I1  three  times  within  3s  (3  times 
change switch state within 3 seconds). 
NOTE1:  For  auto-inclusion  procedure,  first  set  main 
controller into inclusion mode and then connect module to 
power supply. 
NOTE2:  When  connecting  temperature  sensor  to  module 
that  has  already  been  included,  you  have  to  exclude 
module  first.  Switch  off  power  supply,  connect  the  sensor 
and re-include the module. 
 
Module Exclusion/Reset (Removing from 
Z-Wave network) 
 
Connect module to power supply 
 
bring  module  within  maximum  1  meter  (3feet)  of  the 
main controller,  
 
enable add/remove mode on main controller, 
 
press service button S for more than 6 second or 
 
press  push  button  I1  five    times  within  3s  (  5  times 
change  switch  state  within  3  seconds)  in  the  first  60 
seconds  after  the  module  is  connected  to  the  power 
supply. 
By  this  function  all  parameters  of  the  module  are  set  to   
default values and own ID is deleted. 
If  service  button  S  is  pressed  more  than  2  and  less  than 
6second module is excluded, but configuration parameters 
are not set to default values.  
NOTE: If the module is included with parameter 1 value 3, 
4 or 5 and module reset is done, wait at least 30s before 
next inclusion.
 
Association
 
Association  enables  Flush  Dimmer  0-10V  module  to 
transfer  commands  inside  Z-Wave  network  directly 
(without main controller) to other Z-Wave modules. 
Associated Groups
Group  1:  Lifeline  group  (reserved  for  communication  with 
the main controller), 1 node allowed. 
Group  2:  basic  on/off  (triggered  at  change  of  the  input  I1 
state and reflecting its state) up to 16 nodes 
Group 3: start level change/stop level change (triggered at 
change  of  the  input  I1  state  and  reflecting  its  state)  up  to 
16 nodes. Working only when the Parameter no. 1 is set to 
mono stable switch type. 
Group 4: multilevel set (triggered at changes of state/value 
of the Flush Dimmer 0-10V) up to 16 nodes. Working only 
when  the  Parameter  no.  1  is  set  to  mono  stable  switch 
type. 
Group  5:  multilevel  sensor  report  (triggered  at  change  of 
analogue sensor) up to 16 nodes. 
Group  6:  multilevel  sensor  report  (triggered  at  change  of 
temperature sensor) up to 16 nodes. 
Endpoint 1: 
Group 1: Lifeline group, 0 nodes allowed. 
Group  2:  basic  on/off  (triggered  at  change  of  the  input  I1 
state and reflecting its state) up to 16 nodes 
Group  3:  multilevel  set  (triggered  at  changes  of  state  / 
value of the Flush Dimmer 0-10V) up to 16 nodes 
Group  4:  start level  change  /  stop level  change  (triggered 
at change of the input I1 state and reflecting its state) up to 
16 nodes 
End point 2: 
Group 1: Lifeline group, 0 nodes allowed. 
Group  2:  multilevel  sensor  report  (triggered  at  change  of 
analogue sensor) up to 16 nodes. 
End point 3: 
Group 1: Lifeline group, 0 nodes allowed. 
Group  2:  multilevel  sensor  report  (triggered  at  change  of 
temperature sensor) up to 16 nodes. 
 
Configuration parameters 
Parameter no. 1 
– Input 1 type
 
By this parameter the user can set input based on device 
type (switch, potentiometer, 0-10V sensor,..). Available 
configuration parameters (data type is 1 Byte DEC): 
 
default value 0  
 
0  -  mono-stable  switch  type  (push  button) 
–  button 
quick press turns between previous set dimmer value 
and zero) 
 
1 - Bi-stable switch type  
 
2 - Potentiometer (Flush Dimmer 0-10V  is using set 
value the last received from potentiometer or from z-
wave controller) 
 
3 - 0-10V Temperature sensor (regulated output) 
 
4 - 0-10V Illumination sensor (regulated output) 
 
5 - 0-10V General purpose sensor (regulated output) 
NOTE:  After  parameter  change  to  value  3,  4  or  5  first 
exclude  module  (without  setting  parameters  to  default 
value)  then  wait  at  least  30s  and  then  re  include  the 
module! 
Parameter no. 10 - Activate / deactivate functions ALL 
ON / ALL OFF 
 
Available  configuration  parameters  (data  type  is  2  Byte 
DEC): 
 
default value 255 
 
255 - ALL ON active, ALL OFF active. 
 
0 - ALL ON is not active, ALL OFF is not active 
 
1 - ALL ON is not active, ALL OFF active 
 
2 - ALL ON active, ALL OFF is not active 
Flush  Dimmer  0-10V  module  responds  to  commands ALL 
ON  / ALL  OFF  that  may  be  sent  by  the  main  controller  or 
by other controller belonging to the system. 
Parameter  no.  11  -  Automatic  turning  off  output  after 
set time 
 
Available  configuration  parameters  (data  type  is  2  Byte 
DEC): 
 
default value 0 
 
0 - Auto OFF disabled  
 
1 - 32536 = 1second - 32536 seconds Auto OFF 
enabled with define time, step is 1 second. 
Parameter  no.  12  -  Automatic  turning  on  output  after 
set time 
 
Available  configuration  parameters  (data  type  is  2  Byte 
DEC): 
 
default value 0 
 
0 - Auto ON disabled  
 
1  -  32535  =  1second  -  32535  seconds  Auto  ON 
enabled with define time, step is 1 second. 
Parameter  no.  21 
–  Enable/Disable  Double  click 
function
 
If  Double  click  function  is  enabled,  a  fast  double  click  on 
the  push  button  will  set  dimming  power  at  maximum 
dimming  value.  Available  configuration  parameters  (data 
type is 1 Byte DEC): 
 
default value 0 
 
0 - Double click disabled 
 
1 - Double click enabled
 
Valid only if input is set as mono-stable (push button). 
Parameter no. 30 - Saving the state of the device after 
a power failure
 
Available  configuration  parameters  (data  type  is  1  Byte 
DEC): 
 
default value 0 
 
0  -  Flush  Dimmer  0-10V  module  saves  its  state 
before  power  failure  (it  returns  to  the  last  position 
saved before a power failure). 
 
1  -  Flush  Dimmer  0-10V  module  does  not  save  the 
state after a power failure, it returns to "off" position.
 
Parameter no. 52 
– Auto or manual selection
 
This  parameter  is  influencing  on  the  software  only  when 
the value of parameter number 1 is set to value 3, 4 or 5. 
Available  configuration  parameters  (data  type  is  1  Byte 
DEC): 
 
default value 0 
 
0 - Manual 
 
1 - Auto
 
In  manual  mode  regulation  (how  the  input  influence  on 
output) is disabled 
Parameter no. 53  - PID value inside deadband 
Available config. parameters (data type is 1 Byte DEC): 
  default value 0 (PID value equal ZERO) 
  1 - PID value set to LAST VALUE  
NOTE:  When  ZERO  PID  inside  deadband  is  forced  to 
zero. LASTVALUE means that PID remains on same level 
as was before entering into deadband 
 
 
 
 
 
 
 
 
Parameter no. 54  - PID deadband 
Available config. parameters (data type is 1 Byte DEC):  
  default value 1 (1%) 
  0 - 100  0 - 100%, step is 1% 
NOTE: This parameter  defines  the  zone  where  PID is  not 
active.  If  the  temperature  difference  between  actual  and 
setpoint  is  bigger  than  PID  deadband,  then  the  PID  will 
start  to  regulate  the  system,  otherwise  the  PID  is  zero  or 
fixed. 
Parameter no. 55  - Integral sampling time 
Available config. parameters (data type is 1 Byte DEC):  
  default value 5 (5s) 
  0 - 127 - 0s to 127s, step is 1s 
Parameter  defines  the  time  between  samples.  On  each 
sample the controller capture difference between SP-act. 
Parameter no. 56  - P parameter 
Available config. parameters (data type is 2 Byte DEC):  
  default value 100  
  0 -1000 - P value, step is 1 
S 
Service button (used to add 
or remove module from the 
Z-Wave network).