Liebert PS1000RT3-230 Fascicule

Page de 2
Model Number
PS750RT3-230
PS1000RT3-230
PS1500RT3-230
PS2200RT3-230
PS3000RT3-230
Power Rating
750VA/675W
1000VA/900W
1500VA/1350W
2200VA/1980W
3000VA/2700W
Dimensions, W x D x H - mm
Unit
440 x 412 x 88
440 x 657 x 88
Shipping
560 x 595 x 228 
560 x 776 x 228
Weight - kg
Unit
15
19.4
20.9
33.8
37.2
Shipping
18.2
22.6
24.1
38.3
41.5
Input AC Parameters
Surge Protection
220J
Voltage Range Without Battery Operation
165-300, Configurable
Frequency Range
45-65Hz, (±0.5Hz)
Input Socket
IEC-320-C14
IEC-320-C20
Output Receptacles
(8) IEC-320-C13
(8) IEC-320-C13 - (1) IEC-320-C19
Voltage, Normal Mode
220/230/240 VAC, Configurable, ±10%
Voltage, Battery Mode
220/230/240 VAC, Configurable; ±5% Before Low Battery Warning
Transfer Time
4-6 ms, Typical
Waveform
Sinewave
Overload  Warning
 > 100%
Battery Parameters
Type
Valve-Regulated, Nonspillable, Lead Acid
Quantity x Voltage x Ah
2 x 12 x 7.2
3 x 12 x 7.2
3 x 12 x 9
6 x 12 x 7.2
6 x 12 x 9
Backup Time
See Load Autonomy table below
Recharge Time
5 hours to 90% of rated capacity, after full discharge into resistive load
Environmental
Operating Temperature
0°C to 40°C (32°F to 104°F)
Storage Temperature
-15°C to 40°C (5°F to 104°F)
Relative Humidity
0% to 90%, non-condensing
Operating Altitude
Up to 3000m (10,000 ft.) at 35°C (95°F) without derating
Audible Noise
<45 dBA
Agency
Safety
IEC/EN/AS 62040-1-1
Surge
IEC/EN/AS61000-4-2
ESD
IEC/EN/AS61000-4-3
Susceptibility
IEC/EN/AS61000-4-4
Electrical Fast Transient
IEC/EN/AS 62040-2 2nd Ed class A
Emissions
IEC/EN/AS61000-4-6
Conducted Immunity
IEC/EN/AS61000-3-2
Harmonics
IEC/EN/AS61000-4-6
Transportation
ISTA Procedure 1A Certification
Environmental
ROHS compliant
Warranty
2 years standard (+1 year warranty extension available)
Packaging
Multi-Language User Manual on CD, Liebert MultiLink Software on CD, Contact Closure (ML9P9S) Cable
USB Cable, Tower Stand, Mounting Hardware, Rack-Mount Handles, Fixed Mounting Rails, EPO Connector,
Input Power Cord, 2200/3000 only: 2 - (1) Schuko to IEC-320-C19 and (1) UK plug to IEC-320- C19 input cord,
IEC Output Cable, 750/1000/1500 only: 2 - (2) IEC-320-C13,
IEC Output Cable, 2200/3000 only: 3 - (3) IEC-320-C13
Load Autonomy - Liebert PSI 750VA-3000VA
Internal
Battery
Load %
750VA
1000VA
1500VA
2200VA
3000VA
10
84
93
76
82
76
20
45
47
32
44
32
30
25
26
17
19
17
40
15
15
12
14
12
50
11
12
9
11
9
60
9
9
7
9
7
70
7
7
5
7
5
80
5
6
4
5
4
90
4
5
3
4
3
100
4
4
3
3
3
Note: All run times are in minutes, assume fully charged batteries and are typical at 25°C (77°F) with resistive loads.
Locations
Emerson Network Power - Headquarters 
EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 5841 257
marketing.emea@emersonnetworkpower.com
Emerson Network Power - Service EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 9719 045
service.emea@emersonnetworkpower.com
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Tel: +1 614 8880246
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
Tel: +852 2572220
Fax: +852 28029250
Tech Support 
Always  On!  Our  Commitment  to  your  daily 
Business,  provided  by  our  World  Wide  Tech 
support available in 5 Languages (GB, ES, FR, 
IT, DE). 
Toll-free 00-80011554499 
Toll +39 02 98250222 
liebert.upstech@emerson.com 
While every precaution has been taken to ensure 
the accuracy and completeness of this literature, 
Liebert Corporation assumes no responsibility and 
disclaims all liability for damages resulting fromuse 
of this information or for any errors or omissions.
©2010 Liebert Corporation
All rights reserved throughout the world. 
Specifications subject to change without notice.
PSI00-FLY-EN-1209-01
Emerson Network Power
TM
The global leader in enabling 
Business-Critical Continuity
™.
  
AC Power
  
Connectivity
  
DC Power
 
Embedded Computing 
 
Embedded Power
 
Infrastructure Management & Monitoring
 Outside Plant
 Power Switching & Controls
 
Precision Cooling
 
Racks & Integrated Cabinets
 
Services
 
Surge Protection
Emerson Network Power
.com
Emerson, Business-Critical Continuity
TM
 and Emerson 
Network Power are trademarks of Emerson Electric 
Co. or one of its affiliated companies. ©2010 
Emerson Electric Co.
Battery
Backed-up
Receptacles 10A
Voltage Configuration
DIP Swich
RS232
(DB-9) Port
Battery backed-up
receptacle 16A
Resettable Input/Output
Circuit Breakers
Liebert
Intellislot Port
Emergency
Power off
Connector
USB Port
Input Plug
Data-Line
Protection
Liebert
®
 PSI 
Specifications