Zigor TIBER 3KVa 18376 Fascicule

Codes de produits
18376
Page de 2
GENERAL SPECIFICATIONS
Model
TIBER 1
TIBER 1.5
TIBER 2
TIBER 3
Power VA
1000
1500
2000
3000
Power W
    900
 W
1350
1800
2700
GENERAL
Technology
On-Line, double conversion, high frequency, active rectifier
Overload
110-125% 2 min
Efficiency
up to 91%
INPUT
Voltage range
165-295 VAC
Power factor
≥ 0.99 @ nominal voltage (100% load)
Frequency
40Hz ~ 70Hz
Input connections
UK 10A 250V
UK 16A 250VAC
OUTPUT
Power (KVA/KW)
1/0.9
1.5/1.35
2/1.8
3/2.7
Voltage
208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
± 1%
Output frequency 
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
50 Hz ±0.5 % or 60Hz ± 0.5% (Batt. Mode)
Outputs  sockets
IEC*8 C13 10A 250V
Type of wave
Pure Sinewave
Harmonic distortion
(linear load) THD
≤ 2 % THD (Linear Load)
BATTERIES & BACKUP TIME
Standard battery
VRLA: Sealed lead acid maintenance free
Backup time
extended run time options available
Charge time
4 hours recover to 90% capacity
INDICATORS
LCD display
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator
Acoustics
Battery Mode, Low Battery, Overload, Fault
COMMUNICATION
Control software
UPSilon 2000
Communications
RS232 port
Indicators
Low Battery, Overload, Battery is not connected, Overcharge, Site wiring fault, 
EPO enable, Over temperature, Charger failure, Battery Fault, Bypass Out Range,
Bypass Frequency Unstable
SNMP card (optional)
RS232 Ethernet converter
PROTECTION
Protections 
Current limitation, overload, short-circuit and temperature
Automatic bypass
Yes
RFI filter
Yes
STANDARDS
Marks 
CE Marking
OTHERS
Relative humidity
20-90 % RH @ 0- 40°C (non-condensing)
Acoustic level
Less than 50dBA @ 1 Meter
Heat disipation
90W approx.
135W approx.
180W approx.
270W approx.
UPS dimensions DxWxH (mm)
380 x 438 x 88
480 x 438 x 88
600 x 438 x 88
Dimensions U
2U
Shiping dimensions
600x500x240
700x565x240
700x600x240
UPS  weight (Kgs)
12.9
17.6
20.6
28