Eaton TPC2887-3121 Catalogue
eaton.com/epdu 1.800.356.5794
27
Indus
trial ePDUs
(11) Indicator lights
• Main power to system-CB on
• Individual power on to outlets 1-8
• Data acquisition and remote disable
Remote or local control
• Serial RS232 port (DB9 Male) for direct computer or modem
connection
• RS485 input/output for strapping up to 10 systems together
over CAT.5 cable
• Local: one on/off switch for each outlet
• NET SYSTEMS ONLY: RJ45 for network connections (Ethernet)
Remote disable
With the push of a button, disable remote access to the IPC when
needed
Power supply
The IPC3401 series features a full range power supply for
operation at 100-240 Vac input/output
EMI/RFI filtering
• Common mode - line to ground
• Differential mode - line to line
• Filtered inlet isolates noise before entering the system
• Refer to chart 3 on page 40
• IPC3402-2756 and IPC3402-2930 do not have filtering
Spike/surge suppression (TVSS)
• Line to line
• Refer to chart 1 on page 40
• Multi-stage, both MOVs and SAPs
Outlet status
• Query the IPC for Outlet and Watch Dog status
Strapping
• Strapping allows up to 10 IPCs (80 outlets) to be controlled at
one address
• Units are connected together via the RS485 “IN” and “OUT”
connectors
Multiple time delay (MTD)
• Sequence power up and power down to outlets with a one
second time delay (factory set)
• Set power on sequence to any combination of outlets
Set the MTD timing from 1 second to 999 seconds, i.e. 009 = 9
seconds
Software controls
• Multi-platform compatible
• Control via terminal emulation software
• Web interface for browser control
Commands available
• All outlets on/off or specific outlets on/off
• Set up and sequence on/off all outlets
• Create password and unit address
• Outlet naming (8 characters)
• Set up, enable or disable Watch Dog
• Display outlet and Watch Dog timer status
• Automatically receive update outlet status whenever there’s a
change
• Auto-reboot outlet 1 with a five-second delay on restart
Please refer to page 43 for power cable assemblies to match your country specific requirements.
Intelligent Power Control
Catalog Number
Full Load
Receptacles
Circuit
Breaker
EMI/RFI
Filter
Surge
Suppression
Input
Plug
Cord (ft)
Ethernet
Control
Serial
Control
(RS232)
Dimensions
(H x W x D, in)
IPC3401
1920 VA @ 120V~
3840 VA @ 240V~
(8) C13
(2) 20A
20A
270V
C20
Inlet
Power
cables
must be
ordered
separately.
Refer to
page 43
for power
cable
options.
No
Yes
1.7 x 19.0 x 9.5
IPC3401-NET
1920 VA @ 120V~
3840 VA @ 240V~
(8) C13
(2) 20A
20A
270V
C20
Inlet
Yes
Yes
1.7 x 19.0 x 9.5
IPC3402
1920 VA
(8) 5-15R
(1) 20A
20A
270V
C20
Inlet
No
Yes
1.7 x 19.0 x 9.5
IPC3402-NET
1920 VA
(8) 5-15R
(1) 20A
20A
270V
C20
Inlet
Yes
Yes
1.7 x 19.0 x 9.5
IPC3402-A2
1920 VA
(8) 5-20R
(1) 20A
20A
270V
C20
Inlet
No
Yes
1.7 x 19.0 x 9.5
IPC3402-A2-NET
1920 VA
(8) 5-20R
(1) 20A
20A
270V
C20
Inlet
Yes
Yes
1.7 x 19.0 x 9.5
IPC3402-2756
2880 VA
(4) 5-20R,
(4) 5-15R
(1) 20A,
(1) 10A
N/A
270V
L5-30P
10
Yes
Yes
1.7 x 19.0 x 9.5
IPC3402-2930
2880 VA
(8) 5-15R
(1) 20A,
(1) 10A
N/A
270V
L5-30P
10
Yes
Yes
1.7 x 19.0 x 9.5