Lapara LA-ON-2K-RACK Manuel D’Utilisation
www.laparaups.com
ACCESORIES
Remote monitoring & management
¾
LA-
EMD – Environmental Monitoring Device
•
Easy to install together with SNMP manager, plug & play use.
•
Monitor temperature and humidity to protect the most sensitive equipment.
•
It allows 4-contact closure signal for user-defined usage.
•
Management software to remote monitor temperature and humidity status via web browser.
•
Measured temperature range: between 0ºC to 100ºC with an accuracy of
±1.5ºC
•
Measured relative humidity range: between 10% to 90% RH with an accuracy of
±3%
•
Optional smoke alarm available.
Redundant Backup System (LA-RBS)
This RBS (Redundant Backup System) is designed to provide 1+1 redundancy power backup system with cost
efficiency. It integrates 2 UPSs, providing higher reliability that a single UPS could.
efficiency. It integrates 2 UPSs, providing higher reliability that a single UPS could.
•
Max. input current: 10A and 16A.
•
Dual power supply for redundancy.
•
A simple solution that guarantees power continuity for connected equipment.
•
Highly reliable 19” rack design to fit into different working environments.
System configuration
RBS – REDUNDANT BACKUP SYSTEM
MODELO
LA-RBS-10A
LA-RBS-16A
INPUT
Input voltage
Input voltage
208/220/230/240VAC
Acceptable input voltage range
100-280VAC
Input frequency range
40-70 Hz
Nominal input current
10A
16A
OUTPUT
Output voltage
Output voltage
208/220/230/240 VAC
Maximum output current
10A
16A
Master UPS -> slave UPS
10 ms max.
Switching
time
time
Slave UPS -> Master UPS
4 ms max.
CONNECTION
Mains connector
Mains connector
1 x IEC C14
1 x IEC C20
UPS input connectors
2 x IEC C13
2 x IEC C19
UPS output connectors
2 x IEC C14
2 x IEC C20
Load Connecctors
6 x IEC C13
4 x IEC C13 + 1 x IEC C19
INDICATORS
Power LED
Power LED
Green LED
Master UPS LED
Green LED
Slave UPS LED
Green LED
PHYSICAL
Dimensions, D x W x H (mm)
Dimensions, D x W x H (mm)
98 x 438 x 50
Net weight (Kg)
1,8
ENVIRONMENT
Operating temperature & humidity
Operating temperature & humidity
0-90 % RH @ 0 - 40°C (non-condensing)
- 22 -