LOAD REGULATION CHARACTERISTICS 
NO.
LOAD   
CONDITION
OUTPUT LOAD          
12V
+3.3V +5V  +12V -12V +5Vsb 
1
COND.1 
4A 
2
COND.2 
3A 
3
COND.3 
1.5A
1A
1A 
0A 
0.1A 
4
COND.4 
26A 
1A
8A 
0A 
0.1A 
5
COND.5 
1.5A
26A 
8A 
0A
0.1A
6
COND.6 
1A 
5A 
60A 
0A
0.1A
7
COND.7 
3.6A 3.6A 2.6A 0.3A
3A 
8
COND.8 
10A 
9A 
24A  0.25A
1A 
9
COND.9  16.91A 16.91A 49.53A 0.25A 2.48A 
10
COND.10 
10A  10A  60A  0.3A
3A 
               Cond. 10 only at 115Vac/60Hz and less then 1 S 
               Cond. 1 only at 115Vac/60Hz and less then 100 mS 
3.2    REMOTE ON/OFF CONTROL 
The power supply shall accept a logic open collector level which will disable/ 
enable all the output voltage (exclude + 5V standby). 
As logic level is low, outputs voltage were enabled. 
As logic level is high, outputs voltage were disabled. 
Note: 1. Logic high level: 2.0-5.25V while sourcing 0.2mA maximum. 
2. Logic low level: 0-0.5V while sinking 1.6mA maximum. 
3. Rise Time: 15ms maximum (10%-90%). 
3.3  OUTPUT VOLTAGE HOLD-UP TIME      
16.0 mS minimum : at 115V / 60 Hz. (80%LOAD) 
3.4  OPERATION AT NO LOAD 
The power supply shall be capable of being operated with no load on any or 
all outputs without damage. For no load on +3.3V & +5V, the output shall not 
exceed +4.3V & +6.5Vdc and the power supply may shutdown and require 
by remote-control or remove AC power restart. 
3.5  PROTECTION 
3.5.1 Over-voltage protection 
In the event of an over-voltage condition on +3.3 & +5Vdc &+12V the 
power supply shall shutdown and require remote control or remove the AC 
mains input to reset the system. 
+5V : 6.5V (maximum) 
+3.3V : 4.3V (maximum) 
+12V : 15.5V (maximum)