Schneider Electric MGE Galaxy 5000 SUG580A90UL Manuel D’Utilisation

Codes de produits
SUG580A90UL
Page de 15
 
 
Page 1 
12/10/13 
APC by Schneider Electric 
MGE GALAXY 5000 
Data Center Grade Three Phase Uninterruptible Power Supply 
Single Module - Guide Specifications 
40-130 kVA UPS 
 
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE 
(CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE 
ENGINEER TO MEET THE REQUIREMENTS OF THE PROJECT.  COORDINATE THIS SECTION WITH OTHER 
SPECIFICATION SECTIONS IN THE PROJECT MANUAL AND WITH THE DRAWINGS. 
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”, “SUBMIT”, ETC., IT SHALL MEAN 
THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL  “PROVIDE”, “INSTALL”, 
SUBMIT”, ETC., UNLESS OTHERWISE INDICATED. 
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT VERSIONS.  
WHERE APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE INDICATED, THE 
FIRST CHOICE APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES TO THE 1995 
MASTERFORMAT. 
 
 
SECTION [26 33 63] [16611] 
 
SOLID STATE UNINTERRUPTIBLE POWER SUPPLY 
 
 
 
PART 1 - GENERAL 
 
1.1   RELATED 
DOCUMENTS 
 
A. 
Drawings and general provisions of the Contract, including General Conditions, 
[Division 01 - GENERAL REQUIREMENTS] [Division 1 - GENERAL REQUIREMENTS], and 
other applicable specification sections in the Project Manual apply to the work specified in this 
Section. 
 
1.2   SUMMARY 
 
A. 
Scope:  Provide design and engineering, labor, material, equipment, related services, and 
supervision required, including, but not limited to, manufacturing, fabrication, erection, and 
installation for a solid state uninterruptible power supply (UPS) as required for the complete 
performance of the work, and as shown on the Drawings and as herein specified. 
 
B. 
Section Includes:  The work specified in this Section includes, but shall not be limited to, a 
three-phase, on-line, double conversion, solid state UPS.  The UPS shall operate in conjunction 
with the existing building electrical system to provide high quality power conditioning, back-up 
power protection, and distribution for electronic equipment loads.  The system shall consist of a 
solid state IGBT rectifier/inverter, power factor corrected rectifier, a 100 percent rated for 
continuous duty static switch, battery plant, graphical status/control panel, and synchronizing 
circuitry as described herein. 
 
1.3   REFERENCES 
 
A. 
General:  The publications listed below form a part of this Specification to the extent referenced. 
The publications are referred to in the text by the basic designation only.  The edition/revision of 
the referenced publications shall be the latest date as of the date of the Contract Documents, 
unless otherwise specified. 
 
B. 
Institute of Electrical and Electronics Engineers, Inc. (IEEE): 
1. 
ANSI/IEEE C62.41, "Recommended Practice for Surge Voltages in Low-Voltage AC Power 
Circuits" (copyrighted by IEEE, ANSI approved). 
 
C. 
International Organization for Standardization (ISO): 
1. 
ISO 9001, "Quality Management Systems - Requirements."