32
Humidity
Server on: 8% - 85%, maximum dew point 24 °C, maximum rate of change 5 °C/hr.
o
Server off: 8% - 80%, maximum dew point 27 °C.
o
Shipment: 5% - 100%.
o
Design to ASHRAE Class A3, ambient of 35 °C - 40 °C, with relaxed support
Supports a cloud like workload with no acceptable performance degradation (Turbo-Off).
o
Under no circumstance can any combination of worst case workload and configuration result in 
o
system shutdown or design exposure at 40 °C.
Electrical
Models with 675 W AC hot-swap power supplies:
o
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 7.8 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 3.8 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
o
Maximum configuration: 0.77 kVA
o
Models with 460 W AC hot-swap power supplies:
o
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 5.6 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 2.8 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.12 kVA
o
Maximum configuration: 0.53 kVA
o
Models with 460 W AC fixed power supplies:
o
100 - 127 (nominal) V AC; 50 Hz or 60 Hz; 6.0 A
200 - 240 (nominal) V AC; 50 Hz or 60 Hz; 3.0 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.13 kVA
o
Maximum configuration: 0.57 kVA
o
Models with 675 W DC hot-swap power supplies:
o
-40 to -75 (nominal) V DC; 18.34 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.14 kVA
o
Maximum configuration: 0.77 kVA
o
BTU output
Minimum configuration: 406 Btu/hr (119 watts)
o
Maximum configuration: 2627 Btu/hr (770 watts)
o
Noise level
6.5 bels (operating)
o
6.3 bels (idle)
o