Dialight LSA3C4M2G Fascicule

Page de 2
SafeSite
®
LED Linear Fixture
ATEX / IECEx
Mechanical Information
Fixture Weight:
7.9 kg - 1181mm models
4.5 kg - 605mm models
Mounting:
(3) M25 openings 
Supplied with 2 ATEX blanking plugs
Painted Aluminum (6061) Swivel bracket 
included
Electrical Specifications
Operating Voltage:
100-277V AC, 50/60 Hz
Power Consumption:
68W - 1181mm models
36W - 605mm models
Operating Temp:
-20°C to +65°C (-4°F to +140°F)
Harmonics:
IEC 61000-3-2
Surge Protection:
Protection devices capable of 6kV
Verified up to 4kV/2ohms at an 
independent test laboratory
THD:
<20%  
Power Factor:
>0.9 
Construction
Body:
Powder coated low copper alum. 
Lens:
6mm clear toughened glass or
6mm diffused toughened glass
Photometric Information
CRI:
>70 
CCT:
5,000K (cool white) 
IES Files:
Available upon request
All values typical unless otherwise stated
Certifications
Ex d e mb IIB T4 Gb (Ta = -20°C to +65°C)
Ex tb IIIC T135°C Db (Ta = -20°C to +65°C)
Certification numbers : SIRA 12ATEX1215
IECEx SIR 12.0092
ATEX Zones 1, 21 
ATEX Zones 2, 22
CE
IP 66
NEMA 4X
RoHS compliant 
Features & Benefits
L70 rated for >100,000 hours @ 25°C 
5 year full performance warranty 
Instant on/off operation
Universal input (100-277V AC), 50/60Hz
Superior colour rendition index compared to HPS, LPS, MV
Mercury Free and lead free
Temperature compensation technology for longer life
Application
Dialight’s SafeSite
®
LED linear fixture replaces fluorescent lighting fixtures
in hazardous areas, while providing all of the benefits of an LED fixture.
The SafeSite
®
LED linear fixture’s rugged solid state design makes it highly
resistant to shock and vibration. Its fully gasketed IP 66 enclosure makes
it suitable for dusty & wet locations. The SafeSite LED linear’s design
allows for mounting versatility and ease of installation for many lighting
applications.
www.dialight.com
Temperature Ratings
Ambient Temperature Range 
T4 Temperature Code
-20°C to +65°C (-4°F to +140°F)
Dimensions in mm [inches]