Enda EPA141S-R-230 SW Programmable LED ammeter EPA 141S-R ±5 A/AC/DC Assembly dimensions 70 x 29 mm EPA241A-R-230 SW Fiche De Données

Codes de produits
EPA241A-R-230 SW
Page de 3
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected 
parameter in the programming mode.
Programming
key
SET
Used for increasing the setpoint value, as well as the parameter when in programming.
When held down for a few seconds, the change rate accelerates.
Used for decreasing the setpoint value, as well as the parameter when in programming.
When held down for a few seconds, the change rate accelerates. 
Increment
key
Decrement
key
EPA141  PROGRAMMING DIAGRAM
A
SET
ENDA
RMS
DC
AC
OUT
 EPA 141
Means, measured current value is higher than up scale.
Means, measured current value is lower than down scale.
ERROR MESSAGES
Hysteresis value
for upper limit
Delay time for
upper limit alarm
  Upper limit
value
While  holding            key , by  using             and          keys  upper limit value can be adjusted between lower scale and upper
scale that specified with c.t.r.r parameter.This parameter can’t be lower than (
 ) value.
lo.l1 + HYS.l + HYS.U
SET
While  holding            key , by  using              and          keys hysteresis value for upper limit can be adjusted between 0 and  
This parameter can’t be higher than
 
c.tr.r
Up.l1 Lo.l1 Hys.l
 /20.
 ( 
 - 
 - 
 )  value.
Alarm 
 output position
  Lower limit
value
Hysteresis value
for lower limit
   Delay time for
lower limit alarm
Current
transforming
rate
If this key is pressed
hysteresis value 
appears for
 upper limit 
.
If this key is pressed
delay time appears
 for upper limit.
If this key is pressed
upper limit value
appears.
SET
SET
SET
SET
SET
SET
SET
If this key is pressed
lower limit value
appears.
   Alarm 
 output position
If this key is pressed
measuring type
 position appears.
SET
If this key is pressed
current transforming
rate appears.
SET
 If both            &             keys are pressed and held for  5 seconds,programming mode is entered or to running mode is returned. 
  If both keys are
pressed upper limit
value can be adjusted.  
 Measuring Value
SET
SET
&
&
SET
SET
  Or
 Decimal point
      position
SET
PROGRAMMING MODE
ADJUSTING  ALARM  VALUE 
If this key is pressed
hysteresis value 
appears for
 lower limit 
.
If this key is pressed
delay time appears
 for lower limit.
If this key is pressed
alarm output position
 appears.
While  holding            key , by  using              and          keys delay time for upper limit alarm can be adjusted between 0 and
90
 
0 seconds.
While  holding           key , by  using              and          keys delay time for lower limit alarm can be adjusted between 0 and 
90
 
0 seconds.
While  holding            key , by  using              and          keys hysteresis value for upper limit can be adjusted between 0 and 
This parameter can’t be higher than
 
c.tr.r
Up.l1 Lo.l1 Hys.U
 /20.
 ( 
 - 
 - 
 )  value.
While  holding           key , by  using              and          keys alarm output position can be adjusted 
 at alarm condition.
n.o.
N.c..
n.o. is adjusted ,
output relay is powered
 or  
 If  
While  holding            key , by  using              and          keys  current transforming rate can be adjusted between 5.00(/5)  and  
(/5).
If this parameter changes upper limit value sets to upper scale ,lower limit value sets to lower scale and hysteresis 
values set to 0.
9999
While  holding           key , by  using               and          keys measuring type  can be adjusted 
ac
dc
acdc..Three leds 
shows measuring type at the top of the display. 
 , 
  or  
While  holding           key , by  using              and          keys  decimal point  position can be adjusted according to  value of the 
  
c.t.r.r parameter. If  c.t.r.r parameter is; lower than 10, measured value can be shown ( 0.00) or (0.0),  between 10 and 100 
measured value can be shown ( 0.0) or (0), higher than 100 measured value can be shown (0).
SET
SET
While  holding            key , by  using             and          keys  lower limit value can be adjusted between lower scale and upper 
scale that specified with c.t.r.r parameter.This parameter can’t be upper than (
 ) value.
UP.l1 - HYS.U - HYS.L
SET
SET
SET
SET
SET
SET
SET
If this key is pressed
decimal point
 position appears.
If this key is pressed
upper limit value
appears.
If this key is pressed
lower limit value
appears.
  If both keys are
pressed lower limit
value can be adjusted.  
While  holding            key , by  using             and          keys  upper limit value can be adjusted
between lower scale and upper scale that specified with c.t.r.r parameter.This parameter
can’t be lower than (
 ) value.
lo.l1 + HYS.l + HYS.U
SET
While  holding            key , by  using             and          keys  lower limit value can be adjusted
between lower scale and upper scale that specified with c.t.r.r parameter.This parameter
can’t be upper than (
 ) value.
UP.l1 - HYS.U - HYS.L
SET
            
(*) There are only  
EPA141 , EPA141-24 , 
) that has no relay.
              
c.t.r.r , type , d.pnt parameters at the models(
EPA141S , EPA141S-24
If you wait 25 seconds before holding down the keys or power off and power up again, you skip to operation mode.
*
*
*
3./3     EPA141-R-E