Chauvin Arnoux P01157060 Simple Data Logger P01157060 Manuel D’Utilisation

Codes de produits
P01157060
Page de 172
SIMPLE LOGGER II 
 
 
 
English 
 
 
Page 53 
 
MODEL 
ML912 
Electrical 
Channels 
Two 
Input 
Captive MiniFlex
®
 AC Current Flexible Sensors 
Range 
0.5 to 100 A
AC
 
5 to 1,000 A
AC
 
Accuracy 
(50/60Hz) 
0 to 1 A unspecified 
1 to 100 A: 
0 to 5 A unspecified 
5 to 1,000 A: 
 
±(1% of Reading + 0.5 A) 
±(1% of Reading + 1 A) 
Resolution 
0.1 A 
Sample Rate 
64 samples/cycle 
Storage Rate 
Programmable from 125 ms to 1 day 
Storage Modes 
Start/Stop, FIFO and Extended Recording Mode* (XRM™) 
Recording Length 
15 minutes to 8 weeks, programmable using DataView
®
 
Memory 
240,000 measurements (512 KB). 
Recorded data is stored in non-volatile memory and retained 
even if battery is low or removed. 
Communication 
USB 2.0 optically isolated 
Power Source** 
2 x 1.5 V AA-cell alkaline batteries 
Battery Life 
100 hours to > 45 days (dependent on storage rate/recording length) 
Mechanical 
Dimensions 
4.95 x 2.75 x 1.28" (136 x 70 x 32 mm) w/o Sensor 
Weight (with battery) 
8.67 oz (245 g) 
Sensor/Cable Length 
Sensor: 6" (152 mm) / Cable: 6 ft (2 m) 
Case 
UL94-V0 
Vibration 
IEC 68-2-6 (1.5 mm, 10 to 55 Hz) 
Shock 
IEC 68-2-27 (30 G) 
Drop 
IEC 68-2-32 (1 m) 
Environmental 
Operating Temperature 
14° to 122°F (-10° to 50°C) 
Storage Temperature 
-4° to 140°F (-20° to 60°C) 
Relative Humidity 
Up to 85% at 95°F (35°C), Non-condensing 
Altitude 
2000 m 
Safety & Electro-magnetic compatibility 
Safety Rating 
EN 61010-1; 600 V CAT IV; Pollution Degree 2 
Protection Degree 
IP40 
Electro-Magnetic Compatibility 
EN 61326-1 
CE Approved 
Yes 
 
*This specific recording mode has the advantage letting recording continue for a long period, but at the 
expense of the data storage rate. Each time the memory becomes full, in the XRM
TM
 mode, every other item 
of data already recorded is erased, making room for new data. The rate of recording of the new data is 
slowed accordingly. This process continues until recording is deliberately stopped. 
 
**A backup capacitor maintains the date and time for more than 10 seconds to allow completely transparent 
replacement of the batteries. Beyond 10 seconds, the date and time information must be reset (the 
configuration and data are not affected). If the device remains linked to DataView
®
 via a desktop computer, 
the battery life will be 100 hours whatever the recording rate chosen. 
 
*** Input levels exceeding this limit may damage the device.