Beha Amprobe GT-800 PRO KITVDE-tester 4472081 Manuel D’Utilisation
Codes de produits
4472081
GT-600/GT-800 Instruction Manual
28
Touch Current Test (I
T
)
The touch current test measures the leakage current from exposed conductive
parts of tested appliance via test probe PROBE 2 and internal resistance of
approx. 2 k
parts of tested appliance via test probe PROBE 2 and internal resistance of
approx. 2 k
to earth. The device under test is not necessary to be connected to
the test/mains socket of the GT-600/GT-800, it can be also externally powered.
The measurement is carried out by the direct method.
The measurement is carried out by the direct method.
Warning
NEVER carry out this test unless you have first carried out a thorough
visual inspection, followed by a test of the protective bonding resistance
(for class I appliances), and then a test of insulation resistance. You must
verify that these tests have passed before engaging the touch current
test.
(for class I appliances), and then a test of insulation resistance. You must
verify that these tests have passed before engaging the touch current
test.
Caution
Live test! The appliance will be energized at mains voltage. For this
purpose, switch on the appliance. Appliances driven by motors or
equipped with heating units may present a danger for the person
testing (comply with the appliance instruction manual!). Ensure that the
appliance is in a safe condition to run and secure it prior to testing.
equipped with heating units may present a danger for the person
testing (comply with the appliance instruction manual!). Ensure that the
appliance is in a safe condition to run and secure it prior to testing.
Remarks:
Connect the appliance and the test lead according to the figure 18 or 19.
For class I appliances apply the test probe to any metal part not connected to
PE terminal.
For class II appliances apply the test probe to any exposed metalwork on the
appliance.
If the touch current is higher than 2.00 mA for 2 seconds, the test will be
interrupted automatically and “RANGE OVERLOAD” message will be
displayed.
displayed.
The measurement must be performed in both positions of the mains plug,
the greater of the two values obtained must be used.
Figure 18: Touch current test connections at appliance class I