GT-600/GT-800 Instruction Manual 
 
 
Introduction 
 
You have acquired a high-quality measurement instrument manufactured by 
BEHA-AMPROBE, which will enable you to perform repeatable measurements 
for a very long period of time. 
 
The portable appliance tester GT-600/GT-800 is a measurement instrument used 
for safety inspection on electrical appliances complying with VDE 0701-0702 and 
documentation of test results. 
 
Product description: 
 
  Protective bonding resistance measurement (R
PE
), test current 0.2 A AC and 5 
A AC. The test is carried out on plugged and also on permanently connected 
appliances. 
  Insulation resistance measurement (R
ISO
), test voltage 500 VDC (and 250 VDC 
GT-800 only). Appliances class I with heater, class I, class II and class III can be 
tested. 
  Substitute leakage current measurement (I
SUB
), test voltage 45 V AC. 
Appliances class I and class II can be tested. 
  Protective conductor current measurement (I
PE(
)
), differential method
.
 
  Touch current measurement (I
T
) direct method
.
 
  Apparent power, active power, mains voltage, load current and power factor 
PF measurement (P/I
L
). 
  Protective conductor current I
PE
 and load current I
L
 measurement (
), 
clamp method (GT-800 only). 
  IEC CORD test (PE continuity, insulation resistance, L continuity, N continuity, 
L/N shorted). 
  Test of portable RCD (PRCD), PE continuity, TEST button, output insulation 
resistance, PE current, functional test at L disconnection, functional test at N 
disconnection, trip out time at I
N/2
, trip out time at I
N
, trip out time at 5 
I
N
, tripping current (GT-800 only). 
  Protective extra low voltage (PELV) measurement. 
  Safety extra low voltage (SELV) measurement. 
  AUTO Test (13 factory-programmed AUTO-Tests, 17 customer-created AUTO-
Tests) (GT-800 only). 
  Extremely easy operation using the rotary switch and the START/STOP 
button. 
  Automatic start and save function for protective bonding resistance 
measurement allows both-hands measurements on measured objects that 
are difficult to access. 
  Compensation of test lead resistance for protective bonding resistance 
measurement. 
  Calculation of limits for protective bonding resistance. 
  Automatic mains voltage polarity exchange at protective conductor current 
and touch current measurements (GT-800 only). 
  Data memory for over 1000 measurement results. 
  Integrated interface (USB 2.0) for transfer of measurement results to PC. 
  Separate interface (USB 2.0) for connection of optional USB barcode reader, 
USB keyboard, USB memory stick or USB printer.