Beha Amprobe GT-800 STD KITVDE-tester 4472062 Manuel D’Utilisation

Codes de produits
4472062
Page de 76
GT-600/GT-800 Instruction Manual 
24 
 
 
Substitute Leakage Current Test (I
SUB
 
The substitute leakage current test measures the leakage current between L/N 
terminals of test socket and PE terminal of test socket in parallel with PROBE 2 
(at class I, class II). L/N terminals are shorted by the tester for this test. 
 
It is essential to refer to the local appliance test standards and/or guidance 
material for the safe applicability of this test. 
 
Remarks: 
  Connect the appliance and the test lead according to the figure 13 or 14. 
  For class I appliances no probe is required except if there are some metal 
parts on the appliance not connected to PE terminal. 
  For class II appliances apply the test probe to any exposed metalwork on the 
appliance. Do the test for all exposed metal parts on the appliance. 
   
 
 
Figure 13: Substitute leakage current test connections at appliance class I 
 
 
 
Figure 14: Substitute leakage current test connections at appliance class II