Chauvin Arnoux CA6423 GROUNDING METER P01127013 Manuel D’Utilisation

Codes de produits
P01127013
Page de 64
2 2
ELECTRICAL SPECIFICATIONS
Power supply
8 batteries R6 alkaline 1.5 V or 8 accumulators
Range of voltage permitted
8.8...12.5 V
Average battery life
1800 measurements of 15 seconds (at 23°C ± 3 K, with 8
alkaline batteries) permanent test of remaining battery life.
DISPLAY
Display
LCD, 7 segments, height 18 mm,
2000 counts (3½ digits), direct reading in 
Ω
Low battery indicator
"LO BAT" message
Overload indicator
display of  
1 ---
Indicator of lead reversal
- sign preceding the measurement
Indicator of current circuit fault
by flashing red FAULT (E -H) LED
Indicator of voltage circuit fault
Resistance too high
by flashing red HIGH RESISTANCE (E - S) LED
Interference noise
by flashing red HIGH NOISE (E - S) LED
MECHANICAL SPECIFICATIONS
Protection index
IP 54 in accordance with IEC 529 and NF EN 60 529
Free drop
25 cm in accordance with IEC 68-2-32
Shock resistance
50 g
n
 (g
n
 = 9.81 m/s²) in accordance with IEC 68.2.27
Resistance to impacts
IK 04 in accordance with NF EN 50 102
Vibration resistance
± 1 mm, from 10 to 55 Hz in accordance with IEC 68.2.6
Dimensions (W x H x D)
238 x 136 x 150 mm
Connection of leads
on 3 colour coded terminals for 
φ
 4 mm banana plugs or
6 mm spade clips