Settings 
 
23 
4.2.2 Initial settings 
 
 
In this menu the instrument settings and 
measurement parameters and limits can be 
set to initial (factory) values. 
 
Figure 4.3: Initial settings dialogue 
 
Keys: 
 
TEST 
Restores default settings. 
Function selectors 
Exits back to main function menu without changes. 
 
Warning:  
 
‰
 
Customized settings will be lost when this option is used! 
‰
 
If the batteries are removed for more than 1 minute the custom made settings will 
be lost. 
 
The default setup is listed below: 
* model TESTBOY TV 450 (TYPE B) 
 
Instrument setting 
Default value 
Contrast 
As defined and stored by adjustment procedure 
Isc factor  
1.00 
RCD standards 
EN 61008 / EN 61009 
Language English 
Commander Enabled 
 
 
Function 
Sub-function 
Parameters / limit value 
EARTH RE* 
No limit 
R ISO 
No limit 
Utest = 500 V 
Low Ohm Resistance  
 
R LOW
Ω 
No limit 
CONTINUITY* No 
limit 
Z -  LINE 
Fuse type: none selected  
Z -  LOOP 
Fuse type: none selected 
Zs 
rcd
 
Fuse type: none selected 
RCD RCD 
 
 
 
 
 
Nominal differential current: I
ΔN
=30 mA 
RCD type: G  
Test current starting polarity: 
 (0
°) 
Limit contact voltage: 50 V 
Current multiplier: 
×1