Testboy TV 455VDE-tester Testboy TV 455 Manuel D’Utilisation

Codes de produits
Testboy TV 455
Page de 76
TESTBOY TV 450 
Testing RCD 
 
42 
Displayed results: 
x1 ........Step 1 trip-out time (
, I
ΔN, 0º), 
x1 ........Step 2 trip-out time (
, I
ΔN, 180º), 
x5 ........Step 3 trip-out time (
, 5
×IΔN, 0º), 
x5 ........Step 4 trip-out time (
, 5
×IΔN, 180º), 
x½ .......Step 5 trip-out time (
, ½
×IΔN, 0º), 
x½ .......Step 6 trip-out time (
, ½
×IΔN, 180º), 
I .........Step 7 trip-out current (0º), 
I .........Step 8 trip-out current (180º), 
Uc........Contact voltage for rated I
ΔN. 
 
Notes:
 
‰
 
The autotest sequence is immediately stopped if any incorrect condition is 
detected, e.g. excessive Uc or trip-out time out of bounds. 
‰
 
Auto test is finished without x5 tests in case of testing the RCD type A with rated 
residual currents of I
Δn = 300 mA, 500 mA, and 1000 mA. In this case auto test 
result passes if all other results pass, and indications for x5 are omitted. 
‰
 
Tests for sensitivity (I
Δ