Finder 22.34.0.230.4320 Relay IP20 22.34.0.230.4320 Fiche De Données

Codes de produits
22.34.0.230.4320
Page de 10
Technical data
Insulation
22.32 / 22.34
22.44 / 22.64
Rated insulation voltage 
V AC
250
440
440
Pollution degree 
3 *
2
3
Insulation between coil and contact set
Type of insulation
Reinforced 
Reinforced
Overvoltage category 
III
III
Rated impulse voltage
kV (1.2/50 μs)
6
4
Dielectric strength
V AC  4,000
2,000
Insulation between adjacent contacts 
Type of insulation
Basic 
Basic 
Overvoltage category 
III
III
Rated impulse voltage
kV (1.2/50 μs)
4
4
Dielectric strength
V AC  2,500
2,000
Insulation between open contacts
NO contact
NC contact 
NO/NC contacts
Contact gap
mm
3
1.5
3
Overvoltage category 
III
II
III
Rated impulse voltage
kV (1.2/50 μs)
4
2.5
4
Dielectric strength
V AC/kV (1.2/50 μs)
2,500/4
2,000/3
2,000/3
* Only for versions without Auto-On-Off selector. For versions with Auto-On-Off selector pollution degree 2 applies.
Conducted disturbance immunity
Reference standard
Fast transients (burst 5/50 ns, 5  kHz) at coil terminals
EN 61000-4-4
Level 4 (4 kV)
Level 2 (2 kV)
Voltage pulses (surge 1.2/50 μs) at supply terminals (differential mode)
EN 61000-4-5
Level 4 (4 kV)
Level 2 (2 kV)
Short circuit protection
22.32 / 22.34
22.44
22.64
Rated conditional short circuit current
kA
3
3
3
Back-up fuse
A
32 (gL/gG type)
63
80
Terminals
Solid and stranded cable
22.32 / 22.34
22.44 / 22.64
Max. wire size – contact terminals
mm
2
1 x 6 / 2 x 4
1x25 (solid) - 1x16 (stranded)
AWG
1 x 10 / 2 x 12
1x4 (solid) - 1x6 (stranded)
Max. wire size – coil terminals
mm
2
1 x 4 / 2 x 2.5
1x2.5
AWG
1 x 12 / 2 x 14
1x14
Min. wire size – contact and coil terminals
mm
2
1 x 0.2
1x1 (coil) - 1x1.5 (contacts) 
AWG
1 x 24
1x18 (coil) - 1x16 (contacts)
Screw torque 
Nm
0.8
1.2 (coil terminals) - 3.5 (contact terminals)
Wire strip length 
mm
9
10
Other data
22.32
22.34
22.44
22.64
Vibration resistance (10...150)Hz
g
4
4
3
3
Shock resistance
g
10
10
15
15
Power lost to the environment
without contact current W
2
2
5
5
with rated current  
W
4.8
6.3
17
37
NOTE
22.32/22.34: It is suggested an air gap of 9 mm between adjacent relays for installations and working conditions close to the limit (that is, ambient 
temperature > 40 °C, coil operated for a prolonged period of time, all contacts loaded with current > 20 A).
22.44/22.64: The maximum ambient temperature with 3 adjacent contactors is + 40 °C; when more than 3 contactors are installed, it is necessary 
an air gap of 9 mm. 
With 2 adjacent contactors the maximum ambient temperature is + 55 °C; when more than 2 contactors are installed, it is necessary 
an air gap of 9 mm.
5
VI-2014, www
.finder
net.com
22 Series - Modular contactors 25 - 40 - 63 A
22
SERIES
L