Panasonic HE2AN24 PCB Mount Relay 24V 2 NO, DPST-NO HE2AN24 Fiche De Données

Codes de produits
HE2AN24
Page de 6
HE
5
ds_61120_0000_en_he: 061006J
1 Form A Type
MOUNTING METHOD
NOTES
For Cautions for Use, see 
1. Maximum switching power
2. Life curve
3. Contact temperature rise (DC type)
Measured portion: Inside the coil
Contact current: 30 A
100
50
30
20
10
5
1
0.5
30
100
500 1,000
Contact voltage, V
Contact current, A
AC resistive
DC resistive
10
5
100
50
1,000
500
30
35
20
25
10
15
5
0
Contact current, A
No. of operations, 
×
10
4
250 V AC resistive
30 V DC resistive
70
60
50
40
30
20
10
0
100
110
120
20°C
60°C
40°C
Coil applied voltage, %V
Temperature rise, °C
4. Ambient temperature characteristics
Sample: HE2aN-AC120V, 6 pcs.
40
60
80
20
-10
0
-20
-50
-20
-30
x-
x-
Ambient
temperature, °C
Pick-up
voltage
Drop-out
voltage
Rate of
change, %
20
10
1. Plug-in terminal type
2. Screw terminal type
3. Allowable installation wiring size for 
screw terminal types and terminal blocks
Due to the UP terminals, it is possible to 
either directly connect the wires or use 
crimped terminal
M4 screw
Faston No.250
Washer
M4 screw
Washer
1a type
2.6 mm or 5.5 mm
2
2a type
2.0 mm or 3.5 mm
2
1. The dust cover should not be removed 
since doing so may alter the 
characteristics.
2. Avoid use under severe environmental 
conditions, such as high humidity, 
organic gas or in dust, oily locations and 
locations subjected to extremely frequent 
shock or vibrations.
3. When mounting, use spring washers. 
Optimum fastening torque ranges from 5 
kg to 7 kg·cm 
4.5 to 6 pounds·inch
.
4. Firmly insert the receptacles so that 
there is no slack or looseness. To remove 
a receptacle, 2 to 4 kg of pulling strength 
is required. Do not remove more than 
one receptacle at one time.Always 
remove one receptacle at a time and pull 
it straight outwards.
5. Install the relay so that it lies in 
direction A (up-down direction). (Pick-up 
voltage and drop-out voltage values are 
those when installed in direction A.)
6. When using the AC type, the operate 
time due to the in-rush phase is 20 ms or 
more. Therefore, it is necessary for you 
to verify the characteristics for your actual 
circuit. Moreover, the release time for the 
NC side of the 2a1b type requires the 
same verification.
7. When using the push-on blocks for the 
screw terminal type, use crimped 
terminals and tighten the screw-down 
terminals to the torque’s listed below.
8. All AC240V types are rated for double 
coil voltage, both AC 220V AC 240V.
M4.5 screw
147 N-cm to 166.6 N-cm
(15 to 17 kg·cm)
M4 screw
117.6 N-cm to 137 N-cm
(12 to 14 kg·cm)
M3.5 screw
78.4 N-m to 98 N-cm
(8 to 10 kg·cm)