Phoenix Contact Relay Module PLC-RSP- 60DC/21 2966511 2966511 Fiche De Données

Codes de produits
2966511
Page de 11
Nov 9, 2013    2 / 11
Technical data
Coil side
Typical release time
8 ms
Operating voltage display
Yellow LED
Protective circuit
Protection against polarity reversal Polarity protection diode
Protective circuit
Free-wheeling diode Damping diode
Contact side
Contact type
1 PDT
Contact material
AgSnO
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed
for voltages larger than 250 V (L1, L2, L3) between identical
terminal blocks in adjacent modules. Potential bridging is then
carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage
5 V (at 100 mA)
Maximum inrush current
(on request)
Min. switching current
10 mA (at 12 V)
Limiting continuous current
6 A
Interrupting rating (ohmic load) max.
140 W (at 24 V DC)
Interrupting rating (ohmic load) max.
20 W (at 48 V DC)
Interrupting rating (ohmic load) max.
18 W (at 60 V DC)
Interrupting rating (ohmic load) max.
23 W (at 110 V DC)
Interrupting rating (ohmic load) max.
40 W (at 220 V DC)
Interrupting rating (ohmic load) max.
1500 VA (for 250 V AC)
General
Test voltage relay winding/relay contact
4 kV AC (50 Hz, 1 min.)
Operating mode
100% operating factor
Mechanical service life
2 x 10
7
 cycles
Inflammability class according to UL 94
V0
Name
Standards/regulations
Standards/regulations
IEC 60664
Standards/regulations
EN 50178
Standards/regulations
IEC 62103
Pollution degree
3
Surge voltage category
III
Mounting position
Any
Assembly instructions
In rows with zero spacing
Connection data
Connection method
Spring-cage connection
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26