Crydom CKM0620 DIN Rail Solid State Contactor CKM0620 Fiche De Données
Codes de produits
CKM0620
CKM Series
• Ratings from 10A to 30A @ 60 VDC
• Slim 22.5mm (width) package
• Low Leakage
• LED input status indicator
• DC control
• DIN Rail and Panel Mount
• Slim 22.5mm (width) package
• Low Leakage
• LED input status indicator
• DC control
• DIN Rail and Panel Mount
PRODUCT SELECTION
Description
10 A
20 A
30 A
4.5-32 VDC Control
CKM0610
CKM0620
CKM0630
OUTPUT SPECIFICATIONS (1)
Description
CKM0610
CKM0620
CKM0630
Operating Voltage [VDC]
0-60
0-60
0-60
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
0.1
0.1
0.1
Maximum Load Current [Arms]
10
20
30
Maximum Surge Current (10msec) [ADC]
30
60
90
Maximum On-State Voltage Drop @ Rated Current [VDC]
0.2
0.4
0.5
Maximum On-state Resistance @ Rated current (RDS-ON) [ohms]
0.02
0.018
0.016
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
4.0-32 VDC
Maximum Turn-On Voltage
4.0 VDC
Minimum Turn-Off Voltage
1.0 VDC
Maximum Input Current (4)
9 mA @ 5 VDC, 11 mA @ 32 VDC (3)
Maximum Turn-On Time [msec]
1.0
Maximum Turn-Off Time [msec]
1.0
GENERAL SPECIFICATIONS
Description
Parameters
Dielectric Strength, Input/Output/Base (50/60Hz)
2500Vrms
Minimum Insulation Resistance (@ 500 V DC)
10
9
Ohms
Maximum Capacitance, Input/Output
8 pF
Ambient Operating Temperature Range
-40ºC to 80ºC
Ambient Storage Temperature Range
-40ºC to 125ºC
Status Indicator Display
Green LED
Weight (typical)
10 oz. (280g)
Encapsulation
Thermally Conductive Epoxy
Terminals
Box Clamp Type
Maximum Wire Size:
AWG # 10 (3mm)
Recommended Terminal Screw Torque Range:
5.0-6.0 in lb (0.6-0.7 Nm)
Min. Side by Side Spacing
0.8 inch (20mm)
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) Turn-on time for DC control random turn-on versions is 0.02 msec
4) Input circuitry for DC control version incorporates active current limiter.
2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) Turn-on time for DC control random turn-on versions is 0.02 msec
4) Input circuitry for DC control version incorporates active current limiter.