Wago 788-607 Relay 1 changeover 115Vac IP20 788-607 Fiche De Données

Codes de produits
788-607
Page de 1
1
67
1
Relay with 1 changeover contact
with gold contacts and and status indication
(Relay height: 15 mm) 
Nominal input voltage V
N
 115 V, 230 V AC
Relay with 2 changeover contact
with gold contacts and and status indication
(Relay height: 15 mm) 
Nominal input voltage V
N
 115 V, 230 V AC
Load limit curve for 788-412, 788-615 and 788-616
* In order to prevent the gold layer from being damaged 
these values should not be exceeded. Higher 
switching power leads to evaporation of the gold layer. 
The resulting deposits in the enclosure may 
cause sparkovers between the coil and the contact.
Description
V
N
I
N
Item No.
Pack. 
unit
V
N
I
N
Item No.
Pack. 
unit
Relay sockets with pluggable miniature switching 
relay, for DIN 35 rail
115 V AC
8.2 mA
788-607
1
115 V AC
8.2 mA
788-615
1
230 V AC
5 mA
788-608
1
230 V AC
5 mA
788-616
1
Technical Data
Accessories see pages 74 ... 77 + 80 ... 81
Accessories see pages 74 ... 77 + 80 ... 81
Contact material
AgNi + 5μ AU
AgNi + 5μ AU
Input voltage range
V
N
 ± 10 %
V
N
 ± 10 %
Max. switching voltage
250 V AC / 36 V DC*
250 V AC / 36 V DC*
Max. continuous current
50 mA*
2 x 50 mA*
Max. Switching power (resistive)
4 kVA AC, DC see load limit curve
2 x 2 kVA AC, DC see load limit curve
Pull-in/drop-out time typ.
7 ms / 3 ms
7 ms / 3 ms
Nominal operating mode
continious duty
continious duty
Dielectric strength contact-coil
5 kV
5 kV
Dielectric strength open contact
1 kV
1 kV
Dielectric strength contact-contact
2.5 kV
2.5 kV
Nominal voltage acc. to VDE 0110 Part 1/4.97, 
IEC 60664-1
250 V / 4 kV / 3
250 V / 4 kV / 3
Mechanical life
3 x 10
switching operations
3 x 10
switching operations
Degree of protection
IP20
IP20
Ambient operating temperature
-25 °C ... +50 °C
-25 °C ... +50 °C
Storage temperature
-40 °C ... +70 °C
-40 °C ... +70 °C
Dimensions (mm) W x H x L
15 x 54 x 86
15 x 54 x 86
Height from upper-edge of DIN 35 rail
Height from upper-edge of DIN 35 rail
Wire connection
CAGE CLAMP
®
S
CAGE  CLAMP
®
S
Cross sections
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
Stripped lengths
9 ... 10 mm / 0.37 in
9 ... 10 mm / 0.37 in
Approvals
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160, 
EN 50178; degree of protection II; g 
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160, 
EN 50178; degree of protection II; g 
2-pole
resistive load
2 contacts in serie
1 contact
Current (A)
V
oltage (V)
S