Bender RCMA420-D-2 B74043002 Fiche De Données

Codes de produits
B74043002
Page de 40
Operation and setting
17
5.3
Menu structure
All adjustable parameters are listed in the columns "menu item" and "adjusta-
ble parameters". A display-like representation is used to illustrate the param-
eters in the column menu item. Different alarm categories can be assigned to 
the alarm relays K1, K2 via the submenus r1, r2. This is done by activation or 
deactivation of the respective function.
 
Menu
Sub
Menu
Menu 
item
Activa-
tion
Adjustable parameter
 AL
(response -
values)
> I2
- (HI)
I
Δn2
 (Alarm 2)
> I1
- (HI)
I
Δn1
 as % of I
Δn2
(Alarm 1, prewarning)
Hys
-
Hysteresis I
Δn1
 / I
Δn2
 
out
(output con-
trol)
M
ON
Fault memory
1
-
Operating mode K1 (n.c.)
2
-
Operating mode K2 (n.c.)
RL
-
Reload function (memory = 
off )
r1
(K1: (assign-
ment alarm 
category)
 1    Err
ON
Device error at K1
r1     I1
off
Prewarning I
Δn1
 at K1
r1     I2
ON
Alarm I
Δn2
 at K1
 1    tES
ON
Device test
r2
(K2: (assign-
ment alarm 
category)
 2    Err
ON
Device error at K2
r2     I1
off
Prewarning I
Δn1
 at K2
r2     I2
ON
Alarm I
Δn2
 at K2
 2    tES
ON
Device test