Operation and setting
17
5.3
Menu structure
All adjustable parameters are listed in the columns "menu item" and "adjusta-
ble parameters". A display-like representation is used to illustrate the param-
eters in the column menu item. Different alarm categories can be assigned to
the alarm relays K1, K2 via the submenus r1, r2. This is done by activation or
deactivation of the respective function.
ble parameters". A display-like representation is used to illustrate the param-
eters in the column menu item. Different alarm categories can be assigned to
the alarm relays K1, K2 via the submenus r1, r2. This is done by activation or
deactivation of the respective function.
Menu
Sub
Menu
Menu
item
Activa-
tion
Adjustable parameter
AL
(response -
values)
> I2
- (HI)
I
Δn2
(Alarm 2)
> I1
- (HI)
I
Δn1
as % of I
Δn2
(Alarm 1, prewarning)
Hys
-
Hysteresis I
Δn1
/ I
Δn2
out
(output con-
trol)
M
ON
Fault memory
1
-
Operating mode K1 (n.c.)
2
-
Operating mode K2 (n.c.)
RL
-
Reload function (memory =
off )
off )
r1
(K1: (assign-
ment alarm
category)
1 Err
ON
Device error at K1
r1 I1
off
Prewarning I
Δn1
at K1
r1 I2
ON
Alarm I
Δn2
at K1
1 tES
ON
Device test
r2
(K2: (assign-
ment alarm
category)
2 Err
ON
Device error at K2
r2 I1
off
Prewarning I
Δn1
at K2
r2 I2
ON
Alarm I
Δn2
at K2
2 tES
ON
Device test