Entes EPC-12 Fiche De Données

Page de 1
64
ulse  Concentrator
P
EPC-12
EPC-12
ENCLOSURE
DIN  4  (PK27)
IP40
456,4  gr.
10ms
30ms
SUPPLY
190-260V  AC
<  5  VA
45-65  Hz
SPECIFICATIONS
Operating  Voltage
Power  Consumption
Operating  Frequency
AMBIENT  CONDITIONS
Ambient  Temperature
Storing  Temperature
Humidity
CONENCTIONS
0
-25  /  +55 C
STANDARDS
Security  Standards
Terminal  Protection  Class
0
-25  /  +70 C
95%
 
   
    12 
   
   
    RS-485  communication
General
Pulse  collection  from  energy,  water,  gas  meters
different  meter  inputs
Defining  8  different  tariffs  for  each  meter
DST  (Daylight  Saving  Time)  feature
Dimensions
Protection  Class
Weight
Display
PALS
Backlit  2x12  LCD
Minimum  Pulse  Width
Minimum  Time  Between  Pulses
Minimum  Pulse  Period
Maximum  Pulse  Frequency
Maximum  Contact  Resistance
Pulse  Voltage
Trigger  Edge
Total  Counter  Capacity
60ms
16Hz
800  ohm
10  V
Rising  and  Pulse  Width  Control
34359738368
Mounting
Connection  Type
Cable  Thickness  for  Voltage  Connection
Cable  Thickness  for  Pulse  Connection
Cable  Thickness  for  RS-485  Connection
COMMUNICATION
Communication  Interface  /  Protocol
Parity
Adress
Transfer  Speed
Max.  communication  distance
MODBUS  RTU  (RS-485)
None,  odd,  even
1-247
2400-38400  bps
1200m
EN  61010-1
IP  00
Rail  Mount
Terminal  Rail
2
2,5mm
2
1,5mm
Cat  5  cable
Connection  Diagram
EPC-12
NEW
Print  Date:  04.2012
Dimensions
61,6
44,9
48
58
31
,5
26,5
38,9
90
71,2
90
Re
m
ot
M
on
ito
rin
g