Enda ET2011-T-230 PID-CONTROLLER ET2011-T-230 Fiche De Données

Codes de produits
ET2011-T-230
Page de 4
230V AC +%10 -%20, 50/60Hz
24V AC
%10, 50/60Hz
or
Max. 5VA
Power
:
, Si
: 1
²
connector 2.5mm²' screw-terminal
gnal connector
,5mm screw-terminal conenction.
EEPROM (
)
minimum 10 years
Max. 100ohm
1 bit
2
00ms
1
R
: 250V AC, 8A (for resistive load), Selectable as NO+NC Control or Alarm2 output.
elay
°C
Withot load 30.000.000 mechanical operation; 250V AC, on the 8A resistive load 100.000
electrical switching
C/A2 output
ENDA ET2011 PID TEMPERATURE CONTROLLER
*
x
mm
.
77
35
sized
Thank you for choosing
2011 temperature controller.
ENDA ET
TECHNICAL SPECIFICATIONS
* Selectable dual-set value.
* Se
t
lectable thermocouple ypes or Pt100 input.(Selection must be
* Soft-Start feature.
*
(SELF TUNE).
Automatic calculation of PID parameters.
* Selectable heating/cooling control.
* C/A2 Relay output can be programmable as alarm or control output.
*
.
Selectable SSR control output
* Input offset feature.
* In the case of sensor failure periodical running or relay state can be
selected.
*
.
CE marked according to European Norms
Input type
Temperature range
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt 0Rh-Pt) T
1
hermocouple
R (Pt13Rh-Pt) Thermocouple
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
0... 600
0...1300
0... 400
0...1700
0...1700
°C
°C
°C
°C
°C
Accuracy
0, % (
)
5
of full scale
0, % (
)
5
of full scale
1 digit
1 digit
0, % (
)
5
of full scale
1 digit
0, % (
)
5
of full scale
1 digit
0, % (
)
5
of full scale
1 digit
+32... +1112
+32... +2
2
37
+32... +752
+32... +3092
+32... +3092
°F
°F
°F
°F
°F
°C
°F
SSR output
Max 20mA 12Volt (as control output)
SET
°C
SET
ET2011
ENDA
°F
C/A2
SSR
F
Pt 100 Resistance thermometer
Pt 100 Resistance thermometer
EN 60751
EN 60751
-200...600 °C
-328...1112 °F
-
... 00
°C
99.9 3
.0
-
...543
°F
99.9
.0
0,5% (of full scale)
1 digit
0,5% (of full scale)
1 digit
specified in order).
Enter PID parameters of the system if they are known at the beginning.
Otherwise, Self-Tune should be activated.
ENVIRONMENTAL CONDITIONS
Height
Max. 2000m
80
up to 31
decreasing linearly 50
at 40.
%
%
Ambient/storage temperature
Max. Relative humidity
0 ... +50
/
°C -25... +70°C (with no icing)
Rated pollution degree
According to EN 60529
Front panel :
IP65
Rear panel :
IP20
Do not use the device in locations subject to corrosive and flammable gases.
OUTPUTS
Life expectancy for relay
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements
EN 61326-1: 2006
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
CONTROL
Control type
Single set-point and alarm control
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Hysteresis
Output power
Adjustable between 0
and 100 . If Pb=0 , On-Off control is selected.
%
%
%
and 250 seconds
Adjustable between 1
1 and 50
Adjustable between
°C/F
The ratio of power at a set point can be adjusted between 0
and 100
%
%
HOUSING
Housing type
Suitable for flush-panel mounting according to DIN 43 700.
Dimensions
W77xH35xD71mm
Weight
Approx. 200g (after packing)
Self extinguishing plastics.
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or
must not be used.
corrosive materials
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
R
: 250V AC, 16A (for resistive load), Selectable as NO Control or Alarm2 output.
elay
ET
-E
2011
1./4
english