Panasonic AKT7112100J Digital Temperature Controller AKT7112100J Fiche De Données

Codes de produits
AKT7112100J
Page de 20
CT input socket
Power
supply
Heater
CT
  Terminal arrangement 
 
                                                                                                                     
                                                                                                           • OUT 
: Control output 
 • 
RELAY : Relay contact output 
 • 
V/A 
: DC voltage output/ DC current 
 
output 
 • 
EVT 
: Event output [Activated when 
 
Alarm, Loop break alarm or 
 
Heater burnout alarm (option) 
 is 
ON] 
 
• TC : 
Thermocouple 
 
 RTD 
: Resistance temperature detector 
 
• DC 
: DC current or DC voltage 
 
• RS-485 : Serial communication 
 
 
 
 
 
                                                               
(Fig. 4-1) 
 
Caution
 
• Do not leave bits of wire in the KT7 series when wiring, because they could cause fire or malfunction. 
• Insert the connecting cable into the designated connector securely. Otherwise malfunction may occur due
  to imperfect contact. 
• Connect the AC power wire to the designated terminal as is written in this instruction manual, otherwise 
  it may burn and damage the KT7 series. 
• Tighten the terminal screw with the specified torque. Excessive force could damage the terminal screw 
  and deface the case. 
• Use a thermocouple and compensating lead wire that corresponds to the sensor input specification of this unit. 
• Use the 3-wire RTD that corresponds to the sensor input specification of this unit. 
• When using DC voltage and current input types, do not confuse the polarity when wiring. 
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC). 
• Keep input wires (Thermocouple, RTD, etc) away from power source and load wires to avoid external 
interference. 
• To prevent the unit from harmful effects of the unexpected level noise, it is recommended that a surge 
absorber be installed between the electromagnetic switch coils. 
• This unit does not have built-in power switch, circuit breaker or fuse. Therfore, it is necessary to install 
them in the circuit near the external unit. 
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A) 
Note: Tighten the terminal screw properly referring to the table below.
 
Recommended ferrules 
Terminal 
number 
Terminal 
screw 
Ferrules with 
insulation sleeve 
Conductor cross 
sections 
Tightening torque 
Crimping pliers 
AI 0.25-8 YE 
0.2 to 0.25mm
2
 
AI 0.34-8 TQ 
0.25 to 0.34mm
2
 
AI 0.5-8 WH 
0.34 to 0.5mm
2
 
AI 0.75-8 GY 
0.5 to 0.75mm
2
 
AI 1.0-8 RD 
0.75 to 1.0mm
2
 
1 to 4 
M2.6 
AI 1.5-8 BK 
1.0 to 1.5mm
2
 
0.5 to 0.6N・m 
AI 0.25-8 YE 
0.2 to 0.25mm
2
 
AI 0.34-8 TQ 
0.25 to 0.34mm
2
 
5 to 9 
M2.0 
AI 0.5-8 WH 
0.34 to 0.5mm
2
 
0.22 to 0.25N・m 
CRIMPFOX ZA3
CRIMPFOX UD6
 
Option: Heater burnout alarm 
(1) This alarm is not available for detecting heater current 
under phase control. 
(2) This alarm is not available for detecting 3-phase 
heater current. 
(3) Use the current transformer (CT) provided, and pass one 
lead wire of the heater circuit into the hole of the CT. 
(4) When wiring, keep CT wire away from AC sources 
or load wires to avoid the external interference. 
  (Fig. 4-2) 
 
Bottom of the unit 
CT input
Communication
C5 (RS-485)