Siemens SPS starter kit 6ED1057-3BA10-0AA8 6ED1057-3BA10-0AA8 Fiche De Données
Codes de produits
6ED1057-3BA10-0AA8
LOGO! installation and wiring
2.1 Modular LOGO! setup
LOGO!
Manual, 06/2014, A5E33039675
Manual, 06/2014, A5E33039675
29
2.1.2
Maximum setup with expansion modules
LOGO! supports a maximum of 24 digital inputs, 8 analog inputs, 20 digital outputs, and 8
analog outputs (Page 13). You can achieve the maximum setup in different ways as shown
below:
Maximum setup of a LOGO!
with
analog inputs onboard - four in use
LOGO! Base Module, 4 digital modules and 6 analog modules (example)
Maximum setup of a LOGO!
with
analog inputs onboard - two in use
LOGO! Base Module, 4 digital modules and 7 analog modules (example)
Maximum setup of a LOGO!
without
analog inputs onboard (LOGO! 24RCE/24RCEo and LOGO!
230RCE/230RCEo)
LOGO! Base Module, 4 digital modules and 8 analog modules (example)
For LOGO! 12/24RCE/12/24RCEo and LOGO! 24CE/24CEo modules, you can configure
whether the module uses zero, two or four of the four possible analog inputs. AI inputs are
numbered consecutively depending on how many you configure the LOGO! Base Module to
use. If you configure two inputs, they are numbered AI1 and AI2, and correspond to the I7
and I8 input terminals. Subsequent AI expansions modules would begin numbering at AI3. If
you configure four inputs, they are numbered AI1, AI2, AI3, and AI4, and correspond to I7,
I8, I1, and I2 in that order. Subsequent AI expansions modules would begin numbering at