Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Manuel D’Utilisation

Codes de produits
6AV6651-7KA01-3AA4
Page de 364
Easy to communicate between devices 
 
7.5 PROFINET 
 
Easy Book 
140
 
Manual, 03/2014, A5E02486774-AF 
7.5.2 
Configuring the Local/Partner connection path 
After inserting a TSEND_C, TRCV_C or TCON instruction into the user program, the 
inspector window displays the properties of the connection whenever you have selected any 
part of the instruction. Specify the communication parameters in the "Configuration" tab of 
the "Properties" for the communication instruction.  
Table 7- 4 
Configuring the connection path (using the properties of the instruction) 
TCP, ISO-on-TCP, and UDP 
Connection properties 
For the TCP, ISO-on-TCP, and UDP Ethernet 
protocols, use the "Properties" of the instruction 
(TSEND_C, TRCV_C, or TCON) to configure the 
"Local/Partner" connections. 
The illustration shows the "Connection 
properties" of the "Configuration tab" for an ISO-
on-TCP connection. 
 
 
 
 
Note 
When you configure the connection properties for one CPU, STEP 7 allows you either to 
select a specific connection DB in the partner CPU (if one exists), or to create the connection 
DB for the partner CPU. The partner CPU must already have been created for the project 
and cannot be an "unspecified" CPU. 
You must still insert a TSEND_C, TRCV_C or TCON instruction into the user program of the 
partner CPU. When you insert the instruction, select the connection DB that was created by 
the configuration.