7.7 AS-i 
 
Easy Book 
150
 
Manual, 03/2014, A5E02486774-AF 
7.7.2 
Assigning an AS-i address to an AS-i slave 
Configuring the AS-i slave interface 
To configure parameters for the AS-i interface, click the yellow AS-i box on the AS-i slave, 
and the "Properties" tab in the inspector window displays the AS-i interface.  
 
 
AS-i port 
Assigning the AS-i slave address 
In an AS-i network, each device is assigned an AS-i slave address. This address can range 
from 0 through 31; however, address 0 is reserved only for new slave devices. The slave 
addresses are 1(A or B) to 31(A or B) for a total of up to 62 slave devices.  
"Standard" AS-i devices use the entire addresss, having a number address without the A or 
B designation. "A/B node" AS-i devices use the A or B portion of each address, enabling 
each of the 31 addresses to be used twice. The address space range is 1A to 31A plus 1B to 
31B. 
Any address in the range of 1 - 31 can be assigned to an AS-i slave device; in other words, it 
does not matter whether the slaves begin with address 21 or whether the first slave is 
actually given the address 1.