Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Manuel D’Utilisation

Codes de produits
6AV6651-7KA01-3AA4
Page de 364
Easy to use the online tools 
 
11.4 Displaying status of the user program is easy 
 
Easy Book 
260
 
Manual, 03/2014, A5E02486774-AF 
11.4 
Displaying status of the user program is easy 
You can monitor the status of the tags in the LAD and FBD program editors. Use the editor 
bar to display the LAD editor. The editor bar allows you to change the view between the 
open editors without having to open or close the editors.                  
In the toolbar of the program editor, click the "Monitoring on/off" button to display the status 
of your user program. 
 
 
The network in the program editor displays power flow in green. 
You can also right-click on the instruction or parameter to modify the value for the instruction. 
11.5 
Using a watch table for monitoring the CPU 
A watch table allows you to monitor or modify data points while the CPU executes your user 
program. These data points can be inputs (I), outputs (Q), M memory, a DB, or peripheral 
inputs (such as "On:P" or "I 3.4:P"). You cannot accurately monitor the physical outputs 
(such as Q0.0:P) because the monitor function can only display the last value written from Q 
memory and does not read the actual value from the physical outputs.  
The monitoring function does not change the program sequence. It presents you with 
information about the program sequence and the data of the program in the CPU. You can 
also use the "Modify value" function to test the execution of your user program.  
 
 
 
Note 
The digital I/O points used by the high-speed counter (HSC), pulse-width modulation (PWM), 
and pulse-train output (PTO) devices are assigned during device configuration. When digital 
I/O point addresses are assigned to these devices, the values of the assigned I/O point 
addresses cannot be modified by the "Force" function of the watch table. 
 
With a watch table, you can monitor or modify the values of the individual tags, choosing 
from the following options:  
●  At the beginning or the end of the scan cycle 
●  When the CPU changes to STOP mode 
●  "Permanently" (with the value not being reset after a STOP to RUN transition)