Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Manuel D’Utilisation

Codes de produits
6AV6651-7KA01-3AA4
Page de 364
Technical specifications 
 
A.5 Analog I/O modules 
 
Easy Book 
306
 
Manual, 03/2014, A5E02486774-AF 
Technical data 
Relay  
(CPU and SM) 
24 VDC  
(CPU, SM, and SB) 
200 KHZ 24 VDC  
(SB) 
Behavior on RUN to STOP 
Last value or substitute 
value (default value 0) 
Last value or substitute 
value (default value 0) 
Last value or substitute 
value (default value 0) 
Cable length (meters) 
500 m shielded,  
150 m unshielded 
500 m shielded,  
150 m unshielded 
50 m shielded twisted pair 
 
1
  24 VDC 200 KHz SB 
2
  5 VDC 200 KHz SB 
3
  For CPU models with relay outputs, you must install a digital signal board (SB) to use the pulse outputs. 
4
  Depending on your pulse receiver and cable, an additional load resistor (at least 10% of rated current) may improve 
pulse signal quality and noise immunity. 
5
  SB 1223 200 KHz DI 2 / DQ 2: No isolation to inputs 
A.5 
Analog I/O modules 
For a more complete list of modules available for S7-1200, refer to the S7-1200 System 
Manual or to the customer support web site (
). 
A.5.1 
SB 1231 and SB 1232 analog input (AI) and output (AQ) 
Table A- 29  General specifications 
Technical data 
SB 1231 AI 1 x12 bit 
1
  
SB 1232 AQ 1 x 12 bit 
Order number 
6ES7 231-4HA30-0XB0  
6ES7 232-4HA30-0XB0  
Dimensions W x H x D (mm) 
38 x 62 x 21 mm 
38 x 62 x 21 mm 
Weight 
35 grams 
40 grams 
Power dissipation 
0.4 W 
1.5 W 
Current consumption (SM Bus) 
55 mA 
15 mA 
Current consumption (24 VDC) 
None 
40 mA (no load) 
Number of inputs / outputs 
Type 
Voltage or current (differential) 
Voltage or current 
 
1
  To use the SB 1231 AI 1 x analog input, your CPU firmware must be V2.0 or higher.