Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Manuel D’Utilisation

Codes de produits
6AV6651-7KA01-3AA4
Page de 364
Technical specifications 
 
A.8 RTD and Thermocouple modules 
 
Easy Book 
324
 
Manual, 03/2014, A5E02486774-AF 
Technical data 
RTD and Thermocouple (TC) 
Isolation 
Field side to logic 
500 VAC 
Field to 24 VDC 
SM RTD and SM TC: 500 VAC  
(Not applicable for SB RTD and SB TC) 
24 VDC to logic 
SM RTD and SM TC: 500 VAC
  
(Not applicable for SB RTD and SB TC) 
Channel to channel isolation 
 
SM RTD: None  
(Not applicable for SB RTD) 
 
SM TC: 120 VAC  
(Not applicable for SB TC) 
Accuracy (25 °C / -20 to 60 °C) 
See the RTD/TC type tables: 
 
 
Repeatability 
±0.05% FS 
Maximum sensor dissipation 
 
RTD: 0.5 mW 
 
TC: Not applicable 
Measuring principle 
Integrating 
Module update time 
See the RTD/TC filter selection tables: 
 
 
Cold junction error 
 
RTD: Not applicable 
 
TC: ±1.5 °C 
Cable length (meters) 
100 meters to sensor max. 
Wire resistance 
 
RTD: 20 Ω, 2.7 Ω for 10 Ω RTD max. 
 
TC: 100 Ω max. 
A.8.5 
Thermocouple type 
Table A- 54  Thermocouple type (ranges and accuracy) 
Type 
Under range 
minimum
1
 
Nominal 
range low limit 
Nominal 
range high 
limit 
Over range 
maximum
2
 
Normal range 
3, 
accuracy 
@ 25 °C 
Normal range 
3, 4 
accuracy 
-20 °C to 60 °C 
-210.0 °C 
-150.0 °C 
1200.0 °C 
1450.0 °C  ±0.3 °C 
±0.6 °C 
-270.0 °C 
-200.0 °C 
1372.0 °C 
1622.0 °C  ±0.4 °C 
±1.0 °C 
-270.0 °C 
-200.0 °C 
400.0 °C 
540.0 °C 
±0.5 °C 
±1.0 °C 
-270.0 °C 
-200.0 °C 
1000.0 °C 
1200.0 °C  ±0.3 °C 
±0.6 °C 
R & S 
-50.0 °C 
100.0 °C 
1768.0 °C 
2019.0 °C  ±1.0 °C 
±2.5 °C 
0.0 °C 
200.0 °C 
800.0 °C 
-- 
±2.0 °C 
±2.5 °C 
-- 
800.0 °C 
1820.0 °C 
1820.0 °C  ±1.0 °C 
±2.3 °C 
-270.0 °C 
-200.0 °C 
1300.0 °C 
1550.0 °C  ±1.0 °C 
±1.6 °C