Hawker Energy , 6V Ah lead acid battery 4533 4533 Fiche De Données

Codes de produits
4533
Page de 20
 
Products 
5 min 
10 min 
15 min 
30 min 
60 min 
90 min 
5 hr 
8 hr 
10 hr 
20 hr
 
cell 
(2.5Ah)  14.3  8.1  5.9 3.4 1.9  1.4 .48 .32 .26 
.13
 
cell 
(5.0Ah)  28.9  18.1 13.5 7.1 4.0  2.8 1.0 .61 .52 
.26
 
E cell (8.0Ah) 
41.7 
26.4 
19.0 
11.0 
6.2 
4.4 
1.6 
1.0 
.81 
.42
DURATION
4V & 6V Constant current discharge/amps to 1.67Vpc @ 25°C
 
Products 
5 min 
10 min 
15 min 
30 min 
60 min 
90 min 
5 hr 
8 hr 
10 hr 
20 hr
 
D cell (2.5Ah) 
25.3 
15.9 
11.7 
6.8 
3.8 
2.7 
.93 
.60 
.49 
.25
 
X cell (5.0Ah) 
48.8 
32.3 
24.2 
13.8 
7.8 
5.6 
2.0 
1.2 
1.0 
.52
 
E cell (8.0Ah) 
77.8 
51.0 
35.5 
21.1 
12.4 
8.9 
3.1 
2.0 
1.7 
.85
DURATION
4V & 6V Constant power discharge/watts per cell to 1.67Vpc @ 25°C
 
Products 
Cyclic 
Float 
Storage, discharge  
Safety 
C/5 Cycle life 
Float life at
 
 
 
 
& charge 
pressure 
100% DOD 
25°C (20°C)
  
 
 
 
relief 
valve
 
4V D, X, & E 
CV 4.90-5.00 
CV 4.54-4.70 
-40°C to +40°C 
8 psi 
300 
Up to 8 yrs
 
Monobloc 
CC* 
CC* 
 
 
 
(Up to 8 yrs)
 
6V D, X, & E 
CV 7.35-7.50 
CV 6.81-7.05 
-40°C to +40°C 
8 psi 
300 
Up to 8 yrs
 
Monobloc 
CC* 
CC* 
 
 
 
(Up to 8 yrs)
CHARGING PER CELL
TEMPERATURE RANGE
LIFE EXPECTANCY
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 2 atmospheres
Mounting - Each Monobloc is equipped with mounting holes in the cover. The tightening torque for mounting the Monobloc is 25 in-lbs. When using 4 mounting bolts, small spacers 
(washers) 1 to 3 mm thick should be placed between the battery and the mounting surface to prevent bowing or stressing the battery case.
*Users planning to use CC should consult the EnerSys
®
 Application Support Department.
UL Recognised Component. Meets UL 1989
Caution: 
Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys
®
 Customer Service for details.
Charging/Temperature/Life
CYCLON
®
 Battery 4V/6V Monobloc performance specifications
15
Publication No: EN-CYC-SG-003 - December 2008
www.enersys-emea.com