Hawker Energy , 6V Ah lead acid battery 4533 4533 Fiche De Données
Codes de produits
4533
Products
5 min
10 min
15 min
30 min
60 min
90 min
5 hr
8 hr
10 hr
20 hr
D
cell
(2.5Ah) 14.3 8.1 5.9 3.4 1.9 1.4 .48 .32 .26
.13
X
cell
(5.0Ah) 28.9 18.1 13.5 7.1 4.0 2.8 1.0 .61 .52
.26
E cell (8.0Ah)
41.7
26.4
19.0
11.0
6.2
4.4
1.6
1.0
.81
.42
DURATION
4V & 6V Constant current discharge/amps to 1.67Vpc @ 25°C
Products
5 min
10 min
15 min
30 min
60 min
90 min
5 hr
8 hr
10 hr
20 hr
D cell (2.5Ah)
25.3
15.9
11.7
6.8
3.8
2.7
.93
.60
.49
.25
X cell (5.0Ah)
48.8
32.3
24.2
13.8
7.8
5.6
2.0
1.2
1.0
.52
E cell (8.0Ah)
77.8
51.0
35.5
21.1
12.4
8.9
3.1
2.0
1.7
.85
DURATION
4V & 6V Constant power discharge/watts per cell to 1.67Vpc @ 25°C
Products
Cyclic
Float
Storage, discharge
Safety
C/5 Cycle life
Float life at
& charge
pressure
100% DOD
25°C (20°C)
relief
valve
4V D, X, & E
CV 4.90-5.00
CV 4.54-4.70
-40°C to +40°C
8 psi
300
Up to 8 yrs
Monobloc
CC*
CC*
(Up to 8 yrs)
6V D, X, & E
CV 7.35-7.50
CV 6.81-7.05
-40°C to +40°C
8 psi
300
Up to 8 yrs
Monobloc
CC*
CC*
(Up to 8 yrs)
CHARGING PER CELL
TEMPERATURE RANGE
LIFE EXPECTANCY
Maximum recommended storage time before recharge - 24 months @ 25°C or 2.0Vpc, whichever is earlier
Atmospheric pressure range - Vacuum to 2 atmospheres
Mounting - Each Monobloc is equipped with mounting holes in the cover. The tightening torque for mounting the Monobloc is 25 in-lbs. When using 4 mounting bolts, small spacers
(washers) 1 to 3 mm thick should be placed between the battery and the mounting surface to prevent bowing or stressing the battery case.
(washers) 1 to 3 mm thick should be placed between the battery and the mounting surface to prevent bowing or stressing the battery case.
*Users planning to use CC should consult the EnerSys
®
Application Support Department.
UL Recognised Component. Meets UL 1989
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Caution: Batteries contain toxic materials (Pb and H2SO4) • Avoid short circuit • Do not charge in gas-tight container
Sealed-lead rechargeable battery must be recycled or disposed of properly. Contact EnerSys
®
Customer Service for details.
Charging/Temperature/Life
CYCLON
®
Battery 4V/6V Monobloc performance specifications
15
Publication No: EN-CYC-SG-003 - December 2008
www.enersys-emea.com