AVOID THE FOLLOWING
Dead Spots 
Corners
Alcoves
Behind doors
Cold Spots
Concealed pipes or ducts
Stairwells - drafts
Unheated rooms on the other side 
of the wall
Hot Spots
Concealed pipes
Fireplaces
TVs or radios
Lamps
Direct sunlight
Kitchens
Thermostat Installation
• Follow instructions included with your thermostat.
• Locate thermostat five feet above floor on inside wall. 
• Mount directly on wall or vertically mount on outlet box. 
Thermostat should sense average room temperature.
• Set heat anticipator at 0.7 amps. 
• Connect 24 volt thermostat leads to the two (2) yellow 
wires located in service switch junction box, located 
on outer jacket of boiler. See Figure 15, Page 22
 
for 
service switch junction box and thermostat field wiring 
connections.
Connect Circulator Pump Wiring
NOTICE
Label all wires prior to disconnection when servicing 
controls. Wiring errors can cause improper and 
dangerous operation. Verify proper operation after 
servicing.
See Figure 16, Page 24 and Figure 17, Page 25 for service 
switch junction box and circulator pump field wiring 
connections.  If the two 120 volt circulator wire terminals 
inside junction box are not used, leave two wire nuts to 
prevent short circuit.
9 - ELECTRICAL WIRING