HP Performance Optimized Data Center (POD) 40cp Guide De Montage

Page de 21
 
Water quality requirements  12 
Water quality requirements 
Water quality requirements and specifications 
• 
Closed-loop water must not contain any lime scale deposits or loose debris. 
• 
The chilled water temperature to be supplied to the HP POD must be 12º to 24ºC (55º to 75ºF). 
  
 
NOTE:
  Freezing water might cause a blockage and damage to the unit. In outside locations 
subject to freezing temperatures, an additive such as glycol might be necessary to lower the 
freezing point. However, since the heat transfer potential of water with glycol is lower, the HP 
POD must be derated accordingly. 
  
  
 
NOTE:
  The water cycle must be drained completely, and then purged using compressed air 
when storing or transporting at or below freezing temperatures. 
  
 
Acceptable water quality specifications 
Water must be maintained per the following acceptable water quality standards. 
 
Parameter 
Range 
pH 
8.0–10 
Specific conductance at 25ºC 
(77ºF) 
0–2500 µmhos/cm 
Alkalinity ("M" as CaCO
3
150–1000 ppm 
Sulfur (SO
4
0–150 ppm 
Chloride (Cl) 
0–100 ppm 
Hardness (CaCO
3
0–350 ppm 
Calcium hardness (CaCO
3
0–200 ppm 
Magnesium hardness (CaCO
3
0–150 ppm 
Copper (Cu) 
< 0.20 ppm 
Iron (Fe) 
< 3.0 ppm 
Aluminum (Al) 
< 0.50 ppm 
Sodium (Na) 
0–1000 ppm 
Silica (SiO
2
0–150 ppm 
Zinc (Zn) 
< 1.0 ppm 
Manganese (Mn) 
< 0.1 ppm 
Phosphate Ortho- (PO
4
)  
< 3 ppm 
Bacteria 
< 1000 CFU/ml 
Suspended solids 
< 10 ppm 
 
If your water is out of range, consult a water quality expert.