White Rodgers 50M56U-843 Manuel D’Utilisation

Page de 8
2
SPECIFICATIONS 
 
MOUNTING AND WIRING
All  wiring  should  be  installed  by  a  qualified  heating  and  air 
conditioning  contractor  or  licensed  electrician,  according  to 
local and national electrical codes and ordinances.
The control must be secured to an area that will experience a
minimum of vibration and remain below the maximum ambient
temperature  rating  of  176°F.  The  control  is  approved  for
minimum ambient temperatures of -40°F.
When  mounting  the  control,  any  orientation  is  acceptable. 
Choose  a  location  that  will  not  damage,  obstruct  or  place 
stress on the control’s terminations, system wiring harness or 
system components. After finding a suitable location, drill four 
(4) 1/8” holes for mounting control. To ensure proper mounting
hole  locations,  use  the  control  as  a  template.  When  drilling 
the holes, take care so that the transformer, wiring harness or 
other system components are not damaged. Four (4) #8 sheet 
metal screws are provided to complete the installation. 
Refer to the wiring diagram and wiring table when connecting 
the 50M56U-843 control to other components of the system.
UL  approved,  105°C  rated  18  gauge,  stranded,  2/64”  thick
insulation wire is recommended for all low voltage safety circuit 
connections. 
UL  approved  105°C  rated  16  gauge  min.,  stranded,  4/64”
thick  insulation  wire  is  recommended  for  all  line  voltage 
connections. 
After installation or replacement, follow appliance manufacturer’s 
recommended  installation  or  service  instructions  to  ensure 
proper operation.
ELECTRICAL RATINGS [@ 77°F (25°C)]:
Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.45 amp
Relay Load Ratings:
Valve Relay:  1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive)
Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC
Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC
Flame Current Requirements:
Minimum current to insure flame detection: 1 µa DC*
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:
-40° to 176°F (-40° to 80°C)
HUMIDITY RANGE:
MOUNTING:
Surface mount multipoise
Timing Specs: (@ 60 Hz)
 
maximum
Flame Establishing Time: 
0.8 sec
Flame Failure Response Time:
2.0 sec
Gases Approved: Natural, Manufactured, Mixed, Liquified
Petroleum, and LP Gas Air Mixtures are all approved for use.
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise
50M56U-843
Pre-Purge
30
Initial Ignitor Warm-Up
(1st 64 attempts)
17
Maximum Ignitor Warm-Up
19
Ignition Activation Period
2
Trial for Ignition Period
4
Retries
2
Recycles
3
Valve Sequence Period
12
Interpurge
60
Post-Purge
25
Lockout Time
275
Heat Delay-To-Fan-On
30
Heat Delay-To-Fan-Off
100/150*
Cool Delay-To-Fan-On
6
Cool Delay-To-Fan-Off
45
Auto Reset
60 minutes
*These times will vary depending on option switch
position. See OPERATION section for further infor-
mation.
Do  not  short  out  terminals  on  gas  valve  or  primary 
control.  Short  or  incorrect  wiring  may  damage  the 
thermostat.
CAUTION
!
WARNING
!
FIRE HAZARD
•  Do not exceed the specified voltage.
•  Replace existing control with exact model and
dash number.
•  Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
•  If the control has been in direct contact with
water, replace the control.
•  Label all wires before disconnection when serv-
icing controls. Wiring errors can cause improper 
and dangerous operation.
•  Route and secure wiring away from flame.
SHOCK HAZARD
•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and line
hot wires.
EXPLOSION HAZARD
•  Shut off main gas to appliance until installation
is complete.
INSTALLATION