Eaton Electrical Wireless Office Headset SC200 Manuel D’Utilisation

Page de 78
Installation 
3-10 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
 
 
Step 5 – Repeat for other battery cables (if required) 
 
Repeat the above procedure to connect up to three battery strings to an APS6-
059 power system. 
Step 6 – Remove knockout and fit cover 
 
Remove the battery cable knockout(s) on the DC output cover. 
 
 
 
 
 
Battery cable knockout.
 
 
Remove any sharp edges, in particular the remaining knock-out webs.  
Fit the DC output cover. 
Procedure complete 
 
 
Installing the Battery Temperature Sensor (if batteries are fitted) 
 
This section applies to APS3-059, APS3-061 and APS6-059 power systems only. 
 
Each APS3-059, APS3-061 and APS6-059 power system is supplied with a battery 
temperature sensor and standard 2 m (6.5 feet) long cable (factory-fitted to the sensor). 
Longer cables are available from your local Powerware DC product representative or you 
can make up your own.  We strongly recommend limiting the maximum cable length of the 
battery temperature sensor to 20 m (65 feet) because of noise considerations. 
Connecting the Battery Temperature Sensor Cable 
There are two screw-clamp terminal blocks at the rear of APS3-059, APS3-061 and APS6-059 
power systems for terminating the battery temperature sensor cable, as shown below. 
The two terminal blocks are labeled TEMP SENSOR (+) and TEMP SENSOR (-).