Site requirements  13 
• 
Do not treat the water with softeners. Softeners can produce foam, which affects the operation of the 
unit. 
• 
Do not use well water, industrial water, water from cooling circuits, or water contaminated by any 
chemicals or bacteria. 
• 
Do not add potential irritants to the water, such as disinfectants or anti-corrosive compounds. 
• 
The manufacturer recommends installing an in-line filter for the water supply. It is your responsibility to 
determine if a filter should be installed, and if so, its location. The filter cannot be installed inside the HP 
POD 20c and must be compatible with the type of humidifier that is installed. 
For more information, see the Operations and Maintenance Manual or the HP Performance Optimized 
Datacenter 20c Maintenance and Service Guide. 
 
Drainage 
 
Requirement 
Location 
Specification 
Condensate drains 
Hot aisle side (2) 
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 
Chill Water Header drains  Cold aisle side (2) 
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 
Humidifier drain 
Cold aisle side (1) 
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 
 
 
Chilled water supply 
The following are the water quality requirements and specifications: 
• 
Closed-loop water must not contain any lime scale deposits or loose debris. 
• 
The temperature of the chilled water supplied to the HP POD 20c must be 12ºC to 24ºC (55ºF to 75ºF). 
   
 
CAUTION: 
  Freezing water can cause a blockage and damage to the unit. In outside locations 
that are subject to freezing temperatures, an additive such as glycol might be necessary to lower 
the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP 
POD 20c must be de-rated accordingly. 
   
   
 
IMPORTANT:
  The chilled water system piping and heat exchangers must be drained completely, 
and then purged using compressed air when storing or transporting at or below freezing 
temperatures. 
   
   
 
IMPORTANT:
  Operating the chilled water system at the higher end of the acceptable range 
decreases the overall thermal capacity of the POD. 
   
Acceptable water quality specifications 
Water must be maintained per the following acceptable water quality standards. 
 
Parameter 
Range 
pH 
8.0–10 
Specific conductance at 25ºC (77ºF)  10–2500 µmhos 
Alkalinity ("M" as CaCO
3
150–1000 ppm 
Sulfur (SO
4
0–150 ppm 
Chloride (Cl) 
0–100 ppm 
Hardness (CaCO
3
0–350 ppm