Honeywell 805595 Manuel D’Utilisation

Page de 46
IQ8Wireless transponder for wall mounting 
 
FB 798941 / 10.06
 
43
 
 
• 
Do not touch the battery poles or contacts of the RF devices with bare fingers! A layer of 
grease causes transfer resistance to build up between the batteries and contacts. This 
transfer resistance may lead to the FACP prematurely or incorrectly displaying low battery 
voltage (batt. < 30). 
 
• 
Improper storage of the RF devices and batteries may be the cause of such transfer 
resistance (e.g. due to corrosion). If necessary, clean contacts before inserting the 
batteries (e.g. with isopropanol solution). 
 
• 
Only change the batteries as a set (4 items) in order to ensure an equal charge. The 
registered low battery voltage (batt. < 30) on the FACP always relates to the battery with 
the smallest capacity. 
 
• 
For RF devices which register low battery voltage after a long operating time, the 
malfunction may be repaired during inspection by agitating the batteries used for a short 
amount of time (a few hours). When the RF device is activated, no “low battery voltage“ 
message appears. Completely replace the set of batteries for the corresponding RF device!