INSTALLATION INSTRUCTIONS
95- 6940- 12
L8148A,E,J
Aquastat® Relays
APPLICATION
The L8148A,E,J Aquastat® Relays are immersion-type 
controllers for use with forced hydronic heating systems. 
The combination high limit and intermediate switching 
relay works with a low voltage (24V) thermostat to control 
burner and circulator circuits. A call for heat by the 
thermostat starts both the burner and the circulator. 
When boiler-water temperature exceeds the high-limit 
settings, the burner circuit is broken; the circulator 
continues to operate during the thermostat call for heat.
The L8148A controls line-voltage burner circuits; the 
L8148E,J control low-voltage burner circuits; the L8148J 
controls millivoltage burner circuits. All models control 
line-voltage circulator circuits.
L8148A,E,J have provisions for adding low-limit 
controllers; L8148E,J can power valves in multizone 
systems.
L8148E is available with a plug and 50 VA transformer for 
use with Honeywell Smart Valve SV9500/SV9600.
SPECIFICATIONS
Electrical Ratings:
Table 1. Circulator Control Circuit (A):
Table 2. Burner Control Circuit:
Scale Range: 140°F to 240°F (60°C to 116°C) or 180°F 
to 240°F (82°C to 116°C).
Differential: Nonadjustable.
High Limit Dial Stop: Adjustable.
Maximum Pressure on Immersion Well: 255 psi (1758 
kPa).
Maximum Ambient Temperature: 150°F (66°C) with 
1.2A, 24V load; 77°F (25°C) with 1.4A, 24V load.
Maximum Bulb Temperature: 40°F over setpoint, up to 
265°F (4°C over setpoint, up to 129°C).
Thermostat Heat Anticipator Setting: 0.2A.
Material Safety Data Sheets (MSDS): For information 
on heat-conductive compound, see form number 
69-0955.
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
WARNING
Explosion Hazard.
Can cause severe injury, death or property 
damage.
This product is intended for use only in systems 
with a pressure relief valve.
Type
120 Vac
240 Vac
Full Load
7.4
3.7
Locked Rotor
44.4
22.7
Model No.
Voltage
Electrical Rating
L8148A
Line
Same as circulator control 
circuit.
L8148E,J
Low
0.8A maximum at 24 Vac.