Installation/Configuration Notes
• Manual call points have to be mounted visibly along
escape and rescue routes (e.g. exits, passageways,
stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm, meas-
ured from the middle of the manual call point to the
floor, must be maintained.
• Manual call points must be illuminated sufficiently
with daylight or another light source (including emer-
gency lighting, if present).
• Max. one test detector may be used for primary lines
together with automatic detectors. The test detector
is connected at the end of the primary line.
• Further standards, guidelines and planning recom-
mendations regarding the installation location etc.,
should also be taken into consideration (see Fire De-
tection manual).
• Regulations of local fire departments must be ob-
served.
Installation
• Cables can be inserted surface-mounted or flush-
mounted.
ø
 3,4
• Installation in fire hose cabinets is possible in three
ways:
135°
140°
2,5
2
139
1
2
3
10
147
Pos.
Description
1
Installation depth version 1: 36 mm
2
Installation depth version 2: 14 mm
3
Installation depth version 3: approx. 30 mm
Technical Specifications
Electrical
Operating voltage
24 V DC (16.2 V DC . . . 30 V DC)
Current consumption
Specified by the respective se-
curity system
Mechanics
Dimensions (W x H x D)
135 x 135 x 37 mm /
5.31 x 5.31 x 1.4 in.
Housing material
Plastic (ASA)
Colors
Red, RAL 3001
Blue, RAL 5005
Yellow, RAL 1003
Weight
Approx. 224 g
2 | FMC‑120‑DKM Manual Call Points