SSI America Video Gaming Accessories 9200 Manuel D’Utilisation

Page de 68
Model 9200 Programmable Dual-loop Controller
SSi Manual SERIES 9200
31                                              Programmable Dual-loop
Zone Assignments
WARNING: This screen should not be changed without consulting SSi at 800-666-4330.
The zone assignment feature allows the SERIES 9200 program to change set points on all instruments of a
multi-zone furnace.  The SERIES 9200 has up to five (5) temperature and atmosphere zone assignments
available.   The SERIES 9200 programmer looks for appropriate zone assignments whenever a set point is
to be sent to the atmosphere or temperature controller.  The temperature set point is sent to every
instrument number in the temperature zone assignment.
If the 
ZONE_OFF
 (Zone Offset) “opcode” had been used in the program the set point sent to the specified
zone instrument will have the offset added.  For example, a 3-zone pit furnace where the bottom zone
usually has a higher set point. The middle zone and the top zone usually have a lower set point.  The
bottom zone temperature controller is assigned to zone 1, the middle temperature controllers to zone 2,
and the top zone controller to zone 3.
If the first three steps of a program are as shown below, then the bottom zone set point is 1725, the
middle zones are 1750, and the top zone is 1800.
Step
“opcode”
Temperature
Atmosphere
Option
1
ZONE_OFF
50
1
2
ZONE_OFF
25
3
3
SETPT
1750
The first step sets the offset for zone 1 to –25 degrees; therefore, the bottom zone controller would be
sent a set point of 1725 when step 3 is executed.  Likewise step 2 sets the offset for zone 4 to 50 degrees.
The top zone then receives a set point of 1800.  The middle zone controller would receive the 1750. The