Utica Boilers CuB Series Manuel

Page de 4
Engineer:____________________________________________
Project Name:________________________________________
Project Location:______________________________________
Contractor:___________________________________________
APPLICATION:  
Modulating Gas fired water heating boiler for indoor installation. Approved for closet or alcove installations. 
For use with natural or liquefied petroleum (LP/Propane) fuel gases, LP conversion kits available as option. 
Wall mounted – optional floor stand available. All boilers are factory assembled with controls and wiring 
and test fired to ensure dependable performance. Boiler shall be certified for Category I and Category III 
applications.
CERTIFICATION AND APPROVALS:
Copper tube heat exchanger is manufactured and tested in accordance with American Society of Mechanical 
Engineers (ASME) and certified by Canadian Standards Association (CSA). Copper tube heat exchanger is 
tested for maximum allowable working pressure of 43.5 psig in accordance with ASME boiler and pressure 
vessel code, section IV, rules for construction of heating boilers. A 30 psig safety relief valve is shipped 
standard.
BOILERS INCLUDE:
• Wall mount bracket
• Boiler has separate dedicated supply & return water connections to supply hot water directly to an Indirect 
tank.
• Boiler is equipped with an automatic 3 way diverting valve to allow Domestic Hot Water Priority operation.
• Boiler includes an internal pressure activated bypass loop to eliminate the need for primary secondary 
piping and includes an internal factory installed and wired circulator pump.
• Digital Boiler Control:
 
X
Control system is PCB integral controller with LCD digital display that includes graphical interface. 
 
X
Control senses supply water temperature and adjusts the boiler firing rate to deliver amount of heat 
needed.
 
X
Control can sense and display supply water temperature and indicate by icon when boiler is in central 
heating or domestic water mode.
 
X
Control can accept a wired Outdoor Air sensor and has field selectable reset curves
 
X
Control continuously monitors boiler during operation and standby modes. Control receives input data 
from dual temperature sensor, air pressure transducer, and outdoor air temperature sensors (when 
used) to adjust modulation rate accordingly.
 
X
Control can power and accept input from field supplied LWCO device.
P/N 240010784 REV C, [02/2015]
2201 Dwyer Ave.    Utica, NY 13501     www.UticaBoilers.com
Utica Boilers CHB-100/130 - Submittal