StorageTek L180 Manuel D’Utilisation

Page de 56
96047 First 
Edition
2-3
  
Controls and Indicators
Redundant Switch Indicators 
 shows and describes the indicators for the redundant switch: 
 
The redundant switch front panel has the controls and indicators that allow you 
to program settings for the UPS. 
Note: The default settings are suggested for normal use. 
Figure 2-2. Redundant Switch Front Panel 
EPO
Emergency
Power Off
Function
Source A Sensitivity
Source B Sensitivity
Source Preference
Source A Xfer Voltage
Source B Xfer Voltage
Bright
Dim
Off
Normal
Source A
Normal
Narrow
Narrow
Reduced
Source B
Medium
Reduced
Medium
Low
None
Wide
Low
Wide
Source selected
Source OK, but not selected
Source not OK
Level
Redundant Switch
C67350
EPO Switch
Status Indicators
UPS Serial Port Connections
Source Indicators
User Selectable Options 
Function
Default
Bright
Dim
Off
Description 
Source A Sensitivity
Reduced
Normal
Reduced
Low
Sets transfer sensitivity to 
line conditions
Source B Sensitivity
Reduced
Normal
Reduced
Low
Sets transfer sensitivity to 
line conditions
Source Preference
Source A
Source A
Source B
None 
Selects the preferred AC 
source
Source A Xfer Voltage
Medium 
Narrow
Medium 
Wide 
Sets the transfer voltage 
window
Source B Xfer Voltage
Medium 
Narrow
Medium 
Wide 
Sets the transfer voltage 
window
Bright
Dim
Off
Level
Select